280 Parameters
User3 backup
User set 3 has been saved or loaded.
22
User4 backup
User set 4 has been saved or loaded.
23
Enables the saving and restoring of up to four custom sets
of parameter settings.
The set that was in use before powering down the drive is
in use after the next power-up.
Notes:
• Some hardware configuration settings, such as fieldbus
and encoder configuration parameters (groups 14…16,
47, 50…58 and 92…93) are not included in user
parameter sets.
• Parameter changes made after loading a set are not
automatically stored – they must be saved using this
parameter.
• This parameter cannot be changed while the drive is
running
No action
Load or save operation complete; normal operation.
0
User set I/O mode
Load user parameter set using parameters
and
1
Load set 1
Load user parameter set 1.
2
Load set 2
Load user parameter set 2.
3
Load set 3
Load user parameter set 3.
4
Load set 4
Load user parameter set 4.
5
Save to set 1
Save user parameter set 1.
18
Save to set 2
Save user parameter set 2.
19
Save to set 3
Save user parameter set 3.
20
Save to set 4
Save user parameter set 4.
21
When parameter
is set to
, selects the user parameter set together with
as follows:
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
No.
Name/Value
Description
Default
FbEq 16
Status of
source defined
by par.
Status of source
defined by par.
User parameter
set selected
0
0
Set 1
1
0
Set 2
0
1
Set 3
1
1
Set 4
ACS180 FW.book Page 280 Tuesday, March 9, 2021 2:25 PM