278 Parameters
PID
14
Shows which control macro is currently selected. See
chapter
for more information.
To change the macro, use parameter
.
Done
Macro selection complete; normal operation.
0
ABB standard
. For scalar motor control.
1
Hand/Auto
Hand/Auto macro.
5
Hand/PID
Hand/PID macro.
8
Modbus RTU
Modbus RTU
9
Alternate
12
Motor potentiometer
13
PID
14
Restores the original settings of the control program, ie.
parameter default values.
Note:
This parameter cannot be changed while the drive
is running.
Done
Restoring is completed.
0
Restore defaults
All editable parameter values are restored to default
values, except
• motor data and ID run results
• end user texts, such as customized warnings and faults
(external faults and changed), and the drive name
• control panel/PC communication settings
• fieldbus adapter settings
• control macro selection and the parameter defaults
implemented by it
• parameter
and the
differentiated defaults implemented by it.
• user lock configuration parameters
…
8
Clear all
All editable parameter values are restored to default
values, except
• end user texts, such as customized warnings and faults
(external faults and changed), and the drive name
• control panel/PC communication settings
• fieldbus adapter settings (clears entire existing
settings)
• control macro selection and the parameter defaults
implemented by it
• parameter
and the
differentiated defaults implemented by it.
• user lock configuration parameters
…
96.102
.
PC tool communication is interrupted during the restoring.
62
Reset all fieldbus
settings
Restores all fieldbus and communication related settings
to default values.
Note
: Fieldbus, control panel and PC tool communication
are interrupted during the restore.
32
Reset home view
Restores the Home view layout to show the values of the
default parameters defined by the control macro use.
512
No.
Name/Value
Description
Default
FbEq 16