274 Parameters
See parameter
0.00 PID
customer
units
See parameter
0.00
See parameter
200000.00
See parameter
.
See parameter
.
1.00
See parameter
60.0 s
See parameter
.
0.000 s
See parameter
.
0.0 s
See parameter
.
-200000.00
See parameter
.
200000.00
See parameter
The control program compares the absolute value of
parameter
to the deadband
range defined by this parameter. If the absolute value is
within the deadband range for the time period defined by
parameter
, PID's deadband mode
is activated and
is set. Then PID's output is frozen and
bit 2
is set.
If the absolute value is equal or greater than the
deadband range, PID's deadband mode is deactivated.
0.0
0.0…200000.0
Range
1 = 1
Defines the deadband delay for the deadband function.
See parameter
0.0 s
0.0…3600.0 s
Delay
1 = 1 s
See parameter
71.59
See parameter
.
See parameter
. -
See parameter
. 4
76
Various hardware-related settings.
Selects the supply voltage range. This parameter is used
by the drive to determine the nominal voltage of the supply
network. The parameter also affects the current ratings
and the DC voltage control functions (trip and brake
chopper activation limits) of the drive.
WARNING!
An incorrect setting may cause the
motor to rush uncontrollably, or the brake chopper
or resistor to overload.
Note:
The selections shown depend on the hardware of
the drive. If only one voltage range is valid for the drive in
question, it is selected by default.
Automatic / not
selected
No voltage range selected. The drive will not start
modulating before a range is selected, unless parameter
is set to
, in which
case the drive estimates the supply voltage itself.
0
No.
Name/Value
Description
Default
FbEq 16