Parameters 191
When bit 0 of parameter
is 0 (Separate), selects a source that activates
constant frequency 1.
Note:
The default value depends on the selected macro.
See chapter
on page
.
When bit 0 of parameter
is 1 (Packed), this parameter and parameters
and
select three sources whose states activate
constant frequencies as follows:
Always off
0 (always off).
0
Always on
1 (always on).
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
Supervision 1
Bit 0 of
24
Supervision 2
Bit 1 of
25
Supervision 3
Bit 2 of
26
Supervision 4
Bit 3 of
27
Supervision 5
Bit 4 of
28
Supervision 6
Bit 5 of
29
).
-
When bit 0 of parameter
is 0 (Separate), selects a source that activates
constant frequency 2.
When bit 0 of parameter
is 1 (Packed), this parameter and parameters
and
select three sources that are used to
activate constant frequencies. See table at parameter
.
For the selections, see parameter
.
Note:
The default value depends on the selected macro.
See
on page
.
No.
Name/Value
Description
Default
FbEq 16
Source defined
by par.
Source defined
by par.
Source defined
by par.
Constant frequency
active
0
0
0
None
1
0
0
Constant frequency 1
0
1
0
Constant frequency 2
1
1
0
Constant frequency 3
0
0
1
Constant frequency 4
1
0
1
Constant frequency 5
0
1
1
Constant frequency 6
1
1
1
Constant frequency 7
ACS180 FW.book Page 191 Tuesday, March 9, 2021 2:25 PM