Parameters 141
Supervision 2
Bit 1 of
26
Supervision 3
Bit 2 of
27
Supervision 4
Bit 3 of
28
Supervision 5
Bit 4 of
29
Supervision 6
Bit 5 of
30
EFB MCW bit 11
Control word bit 11 received through the embedded
fieldbus interface.
32
EFB connection loss
Detected communication loss of embedded fieldbus
interface changes control mode to EXT2.
35
).
-
Selects the operating mode for external control location
EXT1 in vector motor control mode.
Zero
None.
1
Speed
Speed control. The torque reference used is
(output of the speed reference
chain).
2
Torque
Torque control. The torque reference used is
(output of the torque reference chain).
3
Minimum
Combination of selections
: the torque
selector compares the speed controller output (
Torque reference speed control
) and the torque reference
(
) and selects the smaller of the
two.
If speed error becomes negative, the drive follows the
speed controller output until speed error becomes positive
again. This prevents the drive from accelerating
uncontrollably if the load is lost in torque control.
4
Maximum
Combination of selections
: the torque
selector compares the speed controller output (
Torque reference speed control
) and the torque reference
(
) and selects the greater of the
two.
If speed error becomes positive, the drive follows the
speed controller output until speed error becomes
negative again. This prevents the drive from accelerating
uncontrollably if the load is lost in torque control.
5
Selects the operating mode for external control location
EXT2 in vector motor control mode.
For the selections, see parameter
.
Selects the operating mode for local control in vector
motor control mode.
Speed
Speed control. The torque reference used is
(output of the speed reference
chain).
0
Torque
Torque control. The torque reference used is
(output of the torque reference chain).
1
No.
Name/Value
Description
Default
FbEq 16