Minimum enclosure volume
2) 3)
Breaker type(UL)
1)
Frame
Type ACS180-
04...
in3
dm3
1850
30.3
SU203M-C50
R3
25A0-4
1850
30.3
SU203M-C50
R3
033A-4
4577
75
Contact ABB
R4
038A-4
4577
75
Contact ABB
R4
045A-4
4577
75
Contact ABB
R4
050A-4
1) Ratings in the tables are maximum for the given circuit breaker frame size. Breakers of the same frame
size and interrupting rating with lower current ratings are also allowed.
2) Drives that have an Minimum Enclosure Volume listed must be mounted in an enclosure ≥ Minimum
Enclosure Volume specified in this table.
3) When multiple drives that have an Enclosure Minimum Volume specified are installed in the same
enclosure, minimum volume of the enclosure is determined by largest Enclosure Minimum Volume of
the drives to be placed in the enclosure, plus the volume(s) of each additional drive.
4) Enclosures for R3, 240V and R3, 480V drives must have a solid bottom directly below the drive i.e. fans
(other than internal stirring fans), filters or louvers cannot be mounted directly below the drive but
can be mounted in adjacent areas on the bottom of the enclosure.
■
Manual self-protected combination motor controller – Type E USA
(UL (NEC))
You can use the ABB Type E manual motor protectors (MMP) MS132 & S1-M3-25,
MS165-xx and MS5100-100 as an alternative to the recommended fuses as a means
of branch circuit protection. This is in accordance with the National Electrical Code
(NEC). When the correct ABB Type E manual motor protector is selected from the
table and used for branch circuit protection, the drive is suitable for use in a circuit
capable of delivering no more than 65 kA rms symmetrical amperes at the maximum
rated voltage of the drive. See the table below for the appropriate MMP types and
minimum enclosure volume of IP20 / UL open type drive mounted in an enclosure.
If you use a manual motor protector for the branch circuit protection of the drive,
install the drive into a metal enclosure.
Note: The UL Listing of drive and MMP combinations applies only to drives that
are mounted in appropriately sized metal enclosures that are capable of containing
any drive component failure.
Minimum enclosure volume
4)
MMP type
1) 2) 3)
Frame
Type ACS180-
04...
in3
dm3
1-phase
Un = 208 ... 240 V
890
15
MS132-6.3 & S1-M3-25
5)
R0
02A4-1
890
15
MS132-10 & S1-M3-25
R0
03A7-1
118 Technical data
Содержание ACS180-04S-03A7-1
Страница 1: ...ABB MACHINERY DRIVES ACS180 drives Hardware manual...
Страница 2: ......
Страница 4: ......
Страница 12: ...12...
Страница 24: ...24...
Страница 83: ...Make sure that The motor and the driven equipment are ready for power up Installation checklist 83...
Страница 84: ...84...
Страница 96: ...96...
Страница 146: ...146...
Страница 148: ...Frame R0 148 Dimension drawings...
Страница 149: ...Frame R1 Dimension drawings 149...
Страница 151: ...Frame R3 Dimension drawings 151...
Страница 152: ...Frame R4 152 Dimension drawings...
Страница 160: ...160...
Страница 180: ...Declarations of conformity 180 The Safe torque off function...
Страница 181: ...The Safe torque off function 181...
Страница 182: ...182 The Safe torque off function...
Страница 183: ...The Safe torque off function 183...
Страница 184: ...184...
Страница 187: ...Installation 1 2 N m M4x16 2x 3 3 3 2 2 2 2 Accessories 187...
Страница 189: ...Installation 3 3 2 2 2 3 2 2 N m M4x16 4x 1 Accessories 189...