Supplemental Installation Manual for ACS580-0P
ACS580-0P with Bypass
ACS580-0P with Bypass
Installation
This information is unique to ACS580 with two-contactor bypass (0P+F255+G310)
.
This includes an ACS580 AC adjustable frequency drive packaged with circuit
breaker with disconnect and a two-contactor bypass. Refer to the Electrical
Installation - North America in the ACS580 Hardware Manual for all other
information.
Failure to observe the warnings and instructions may cause
malfunction or personal hazard.
WARNING!
WARNING!
When the ACS580 with bypass is connected to the line power, the Motor
Terminals T1, T2, and T3 are live even if the motor is not running. Do not make any
connections when the ACS580 with bypass is connected to the line. Disconnect and
lock out power to the drive before servicing the drive. Failure to disconnect power
may cause serious injury or death.
1. Install wiring
WARNING!
• Metal shavings or debris in the enclosure can damage electrical equipment and
create a hazardous condition. Where parts, such as conduit plates require cutting or
drilling, first remove the part. If that is not practical, cover nearby electrical
components to protect them from all shavings or debris.
• Do not connect or disconnect input or output power wiring, or control wires, when
power is applied.
• Never connect line voltage to drive output Terminals T1, T2, and T3.
• Do not make any voltage tolerance tests (Hi Pot or Megger) on any part of the unit.
Disconnect motor wires before taking any measurements in the motor or motor
wires.
• Make sure that power factor correction capacitors are not connected between the
drive and the motor.