272 Parameters
Protect
Detection of low inlet pressure produces an alarm after the
delay defined by parameter
expires. The
pump speed is reduced to the speed defined by
.
3
81.02
AI measure inlet
Selects the analog input (or signal source) for pump inlet
pressure measurement.
AI1 scaled
(see page
).
1073742341
AI2 scaled
(see page
).
1073742343
AI3 scaled
(see page
).
1073742345
AI4 scaled
(see page
).
1073742347
AI5 scaled
(see page
).
1073742349
Pointer
Value pointer setting (see
on page
).
-
81.03
AI in low level
Pressure limit for primary inlet pressure supervision. See
parameter
0.00 … 32767.00
bar
Pressure limit.
100 = 1 bar
No.
Name/Value
Description
FbEq
Measured inlet
pressure
Time
Speed reference
Time
, bit 2
0
1
, bit 16
0
1
Time
Time
, bit 4
0
1
Time
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...