Parameters 235
115200
115.2 kbit/s.
6
58.05
Parity
Selects the number of the data bits, the use and type of the
parity bit, and the number of the stop bits.
8 none 1
Eight data bits, no parity bit, one stop bit.
0
8 none 2
Eight data bits, no parity bit, two stop bits.
1
8 even 1
Eight data bits, even parity bit, one stop bit.
2
8 odd 1
Eight data bits, odd parity bit, one stop bit.
3
58.06
Control profile
Selects the communication profile used by the Modbus
protocol.
ABB Classic
ABB Drives profile, classic version.
0
ABB Enhanced
ABB Drives profile, enhanced version.
1
DCU 16-bit
DCU 16-bit profile.
2
DCU 32-bit
DCU 32-bit profile.
3
58.07
Comm loss t out
Defines the timeout limit for EFB communication loss
monitoring. If a communication break exceeds the timeout
limit, the function proceeds with the action defined with
parameter
. See also parameter
.
0…60000 ms
Timeout calculation factor. The actual timeout value is
calculated as follows:
Comm loss timeout × 100 ms
Example:
If you set this value to 22, the actual timeout value
will be: 22 × 100 ms = 2 200 ms.
100 = 1 ms
58.08
Comm loss mode
Enables/disables EFB communication loss monitoring and
defines which of the Modbus register accesses resets the
timeout counter. See parameter
None
EFB communication loss monitoring is disabled.
0
Any message
EFB communication loss monitoring is enabled. Any Modbus
request resets the timeout counter.
1
Ctrl write
EFB communication loss monitoring is enabled. Writing to
control or reference word resets the timeout counter.
2
58.09
Comm loss action
Defines the drive operation after the EFB communication
loss monitoring awakes. See parameters
and
.
None
No action.
0
Fault
Drive trips on fault
1
Safe speed
Drive generates alarm
takes the safe speed into use (see parameter
).
2
Last speed
Drive generates alarm
takes the last speed into use (average over the previous
10 seconds).
3
58.10
Refresh settings
Refreshes the settings of parameters
…
Done
Initial value. The value is restored after the refresh is done.
0
Refresh
Refresh.
1
No.
Name/Value
Description
FbEq
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...