Fieldbus control through a fieldbus adapter 375
Contents of the fieldbus Status word
The upper case boldface text refers to the states shown in the state diagram
(page
.
Bit
Name
Value STATE/Description
0
Ready to switch
ON
1
READY TO SWITCH ON
.
0
NOT READY TO SWITCH ON
.
1
Ready run
1
READY TO OPERATE
.
0
OFF1 ACTIVE
.
2
Ready ref
1
OPERATION D
.
0
OPERATION INHIBITED
.
3
Tripped
1
FAULT
.
0
No fault.
4
Off 2 inactive
1
OFF2 inactive.
0
OFF2 ACTIVE
.
5
Off 3 inactive
1
OFF3 inactive.
0
OFF3 ACTIVE
.
6
Switch-on
inhibited
1
SWITCH-ON INHIBITED
.
0
–
7
Warning
1
Warning active.
0
No warning active.
8
At setpoint
1
OPERATING
. Actual value equals reference = is within tolerance
limits
0
Actual value differs from reference = is outside tolerance limits.
9
Remote
1
Drive control location: REMOTE (EXT1 or EXT2).
0
Drive control location: LOCAL.
10
Above limit
-
.
11
User bit 0
-
See parameter
12
User bit 1
-
See parameter
.
13
User bit 2
-
See parameter
.
14
User bit 3
-
See parameter
.
15
Reserved
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...