238 Parameters
Source selection (see
on
page
-
Selects the primary source used for pump outlet
pressure measurement.
Not selected
None.
0
AI1 scaled
Parameter
.
1
AI2 scaled
Parameter
.
2
Freq in scaled
3
AI1 percent
.
8
AI2 percent
.
9
Feedback data
storage
Parameter
10
Source selection (see
on
page
-
Defines the height difference between inlet and
outlet pressure sensors for flow calculation.
0.00 m
0.00...
32767.00 m
Sensors height difference.
1 = 1 m
Selects the unit of pressure.
bar
Pressure.
0
kPa
Kilo pascal.
1
psi
Pound per square inch.
2
Pa
Pascal.
3
Selects the unit of flow.
The selection affects total flow and specific
energy units.
m
3
/h
Cubic meter per hour.
0
I/s
Liters per second.
1
gpm
US gallon per minute.
2
Selects the unit of estimated head points,
sensors height difference and pump inlet/outlet
diameters.
centimeters
Length unit in centimeter.
69
meters
Length unit in meter.
72
Inches
Length unit in inch.
73
feet
Length unit in feet.
27
Selects the unit of density.
kg/m
3
Kilograms per cubic meter.
0
kg/l
Kilograms per liter.
1
No.
Name/Value
Description
Def/
FbEq16
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...