Fault tracing 361
D406
Maximum flow
protection
Programmable fault:
Actual flow is exceeded the
defined fault level.
Check the system for leakages.
Check flow protection settings in
parameters
,
D407
Minimum flow
protection
Programmable fault:
Actual flow is below the
defined fault level.
Check that the inlet and outlet valves
are open.
Check flow protection settings in
parameters
D408
Outlet minimum
pressure
Programmable fault:
Outlet minimum pressure
protection
The measured outlet pressure
is below the defined fault limit.
Check the pump outlet for leakages.
Check the configuration of outlet
pressure protection.
See parameter
and
.
D409
Outlet maximum
pressure
Programmable fault:
Outlet maximum pressure
protection
The measured outlet pressure
is above the defined fault limit.
Check the pump outlet for blockages
or closed valve.
Check the configuration of outlet
pressure protection.
See parameters
.
D40A
Inlet minimum
pressure
Programmable fault:
Inlet minimum pressure
protection
The measured inlet pressure is
below the defined fault level.
Check the pump inlet for blockages or
closed valve.
Check the configuration of inlet
pressure protection.
See parameters
and
.
D50B
Pipe fill-timeout
Programmable fault:
Soft pipe fill has reached
timeout limit. The PID output is
not reached the setpoint after
reference ramping is ended
and the timeout limit is
elapsed.
Check the pipe for possible leakage.
See parameter
and
.
0xD401
Max cleaning fault
Programmable fault:
The maximum number of
cleanings are reached in the
defined time. The pump
cleaning is unable to clean the
pump and hence, manual
cleaning is required.
Check the pump for blockages.
Clean the pump manually if needed.
Check parameters
to
.
0xD402
High level
Programmable fault:
Water level is reached the high
level limit. Level control is
unable to control the level for
the following reasons:
• running out of pumping
capacity or
• analog feedback sensor
failure.
Check the analog level sensor.
Check that all pumps are operating
normally.
Check parameters
and
Code
(hex)
Fault / Aux. code
Cause
What to do
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...