Parameters 279
Defines the constant time interval between cleaning cycles.
This parameter is used only when cleaning is triggered by
time interval.
02:00:00h
00:00:00...45:12:15
h
Time
1 = 1h
Defines the number of cycles performed in cleaning program.
For example, 1 cycle = 1 f 1 reverse step.
3
1...65535
Value range
Defines the speed/frequency step size in pump cleaning.
Cleaning speed step is same for positive and negative
directions.
Note:
If you have disabled the negative rotation direction by
speed limits, the pump cleaning does not operate in the
negative direction.
80
0...100%
Percentage of the cleaning speed/frequency value.
1 = 1%
Defines the time required for the drive to reach cleaning
speed set by parameter
3.000
0.000...60.000 s
Time
1 = 1s
Defines the time required for the drive to reach zero speed
from the cleaning speed set by parameter
.
3.000
0.000...60.000 s
Time
1 = 1s
Defines the cleaning On time when the drive is running at
cleaning speed set by parameter
.
10.000
0.000...1000.000 s
Time
1 = 1s
Defines the cleaning Off time when the drive stays at zero
speed between positive and negative pulses and after one
cleaning cycle before starting a new cleaning cycle.
5.000
0.000...1000.000 s
Time
1 = 1s
Activates the cleaning count monitoring, and selects the
action it takes if it detects too many cleaning starts within the
time defined by parameter
See section
(page
No action
No action
0
Warning
Warning
1
Fault
Fault
2
Defines the time for cleaning count monitoring.
See section
(page
00:01:00h
00:00:00...45:12:15
h
Time
1 = 1h
Defines the maximum cleaning counts allowed.
See section
(page
5
0...30
Maximum cleaning counts.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...