356 Fault tracing
64B2
User set fault
Loading of user parameter set
failed because
• requested set does not exist
• set is not compatible with
control program
• drive was switched off
during loading.
Ensure that a valid user parameter
set exists. Reload if uncertain.
64E1
Kernel overload
Operating system error.
Reboot the control unit (using
parameter
)
or by cycling power. If the problem
persists, contact your local ABB
representative.
64B1
Fault reset
A fault has been reset. The
cause of the fault no longer
exists and the fault reset has
been requested and
completed.
Informative fault.
6581
Parameter system
Parameter load or save failed.
Try forcing a save using parameter
Retry.
6591
Backup/Restore
timeout
During backup creating or
restoring operation a panel or
PC-tool has failed to
communicate with the drive as
part this operation.
Check panel or PC-tool
communication and if it is still in
backup or restore state.
65A1
FBA A parameter
conflict
The drive does not have a
functionality requested by
PLC, or requested functionality
has not been activated.
Check PLC programming.
Check settings of parameter groups
.
6681
EFB comm loss
Programmable fault:
Communication break in
embedded fieldbus (EFB)
communication.
Check the status of the fieldbus
master (online/offline/error etc.).
Check cable connections to the
EIA-485/X5 terminals 29, 30 and 31
on the control unit.
6682
EFB config file
Embedded fieldbus (EFB)
configuration file could not be
read.
Contact your local ABB
representative.
6683
EFB invalid
parameterization
Embedded fieldbus (EFB)
parameter settings
inconsistent or not compatible
with selected protocol.
Check the settings in parameter
group
6684
EFB load fault
Embedded fieldbus (EFB)
protocol firmware could not be
loaded.
Contact your local ABB
representative.
Version mismatch between
EFB protocol firmware and
drive firmware.
6685
EFB fault 2
Fault reserved for the EFB
protocol application.
Check the documentation of the
protocol.
6686
EFB fault 3
Fault reserved for the EFB
protocol application.
Check the documentation of the
protocol.
Code
(hex)
Fault / Aux. code
Cause
What to do
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...