348 Fault tracing
AFE9
Start delay
The start delay is active and
the drive will start the motor
after a predefined delay.
Informative warning. See parameter
.
AFED
Run permissive
Run permissive is keeping the
drive from running the motor.
Check the setting of (and source
selected by) parameter
.
AFEE
Start interlock 1
Start interlock 1 is keeping the
drive from starting.
Check the signal source selected for
parameter
.
AFEF
Start interlock 2
Start interlock 2 is keeping the
drive from starting.
Check the signal source selected for
parameter
.
AFF0
Start interlock 3
Start interlock 3 is keeping the
drive from starting.
Check the signal source selected for
parameter
.
AFF1
Start interlock 4
Start interlock 4 is keeping the
drive from starting.
Check the signal source selected for
parameter
.
AFF6
Identification run
Motor ID run will occur at next
start.
Informative warning.
AFF8
Motor heating active
Pre-heating is being performed Informative warning.
Motor pre-heating is active. Current
specified by parameter
is being passed through
the motor.
B5A0
STO event
Programmable event:
Safe torque off function is
active, ie. safety circuit
signal(s) connected to
connector STO is lost.
Informative warning.
Check safety circuit connections. For
more information, see chapter
The Safe
torque off function
in the
Hardware
manual
of the drive and description of
D405
Pipe fill-timeout
Programmable warning:
Soft pipe fill is reached the
timeout limit. The PID output is
not reached the setpoint after
reference ramping is ended
and timeout limit is elapsed.
Check the pipe for possible leakage.
See parameter
.
D501
No more available
PFC motors
No more PFC motors can be
started because they can be
interlocked or in the Hand
mode.
Check that there are no interlocked
PFC motors, see parameters:
If all motors are in use, the PFC system
is not adequately dimensioned to
handle the demand.
D502
All motors interlocked All the motors in the PFC
system are interlocked.
Check that there are no interlocked
PFC motors, see parameters
D503
VSD controlled PFC
motor interlocked
The motor connected to the
drive is interlocked
(unavailable).
Motor connected to the drive is
interlocked and thus cannot be started.
Remove the corresponding interlock to
start the drive controlled PFC motor.
See parameters
.
0xD505 Max cleaning warning
Programmable warning:
Maximum number of cleanings
are reached in defined time.
The Pump cleaning is unable
to clean the pump and hence,
manual cleaning is required.
Check the pump for blockages.
Clean the pump manually if needed.
Check parameters
to
Code
(hex)
Warning / Aux. code Cause
What to do
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...