272 Parameters
Defines the pump outlet pipe diameter.
0.100
0.010...
32767.000 cm
Pump outlet pipe diameter.
1 = 1 cm
Defines the speed limit below which flow is not calculated.
5.00
0.00...32767.00 Hz
Minimum speed limit for flow calculation.
1 = 1 Hz
Defines the density of the fluid to be pumped for the flow
calculation function.
1000.00
0.00...
32767.00 kg/m
3
Fluid density.
1 = 1 kg/m
3
Resets the signal
Not selected
Total flow reset is not selected.
0
Reset
Resets cumulative flow counter.
Note:
The value reverts automatically to
after
the flow is reset.
1
Defines the head at point 1 of the HQ performance curve.
See section
0.00
0.00...32767.00 m
Head at point 1 of the HQ curve.
1 = 1 m
Defines the head at point 2 of the HQ performance curve.
See parameter
(page
).
0.00
Defines the head at point 3 of the HQ performance curve.
See parameter
(page
).
0.00
Defines the head at point 4 of the HQ performance curve.
See parameter
(page
).
0.00
Defines the head at point 5 of the HQ performance curve.
See parameter
(page
).
0.00
Defines the power input of pump at point 1 on the PQ
performance curve.
See section
0.00
0.00...32767.00 kW Power input of pump at point 1.
Defines the power input of pump at point 2 on the PQ
performance curve.
See parameter
(page
).
0.00
Defines the power input of pump at point 3 on the PQ
performance curve.
See parameter
(page
).
0.00
Defines the power input of pump at point 4 on the PQ
performance curve.
See parameter
(page
).
0.00
Defines the power input of pump at point 5 on the PQ
performance curve.
See parameter
(page
).
0.00
Defines the flow rate at point 1 on the PQ performance curve.
See section
0.00
0.00...
200000.00 m
3
/h
Flow rate at point 1 of the PQ curve.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...