Parameters 119
Contains the values of relay outputs that are used instead of
the connected signals if selected in parameter
. Bit 0 is the forced value for RO1.
0000h…FFFFh
Forced RO values.
1 = 1
Selects a drive signal to be connected to relay output RO1.
Not energized
Output is not energized.
0
Energized
Output is energized.
1
Ready run
Bit 1 of
(see page
2
Enabled
Bit 0 of
4
Started
Bit 5 of
5
Magnetized
Bit 1 of
6
Running
Bit 6 of
7
Ready ref
Bit 2 of
(see page
8
At setpoint
Bit 8 of
(see page
9
Reverse
Bit 2 of
(see page
).
10
Zero speed
Bit 0 of
(see page
).
11
Above limit
Bit 10 of
(see page
12
Warning
Bit 7 of
(see page
13
Fault
Bit 3 of
(see page
14
Fault (-1)
Inverted bit 3 of
).
15
Fault/Warning
Bit 3 of
OR bit 7 of
(see page
).
16
Overcurrent
Fault
has occurred.
17
Overvoltage
Fault
has occurred.
18
Drive temp
Fault
or
or
or
has occurred.
19
Undervoltage
Fault
has occurred.
20
Motor temp
Fault
or
has occurred.
21
Reserved
22
Ext2 active
Bit 11 of
23
Remote control
Bit 9 of
(see page
24
Reserved
25…26
Timed function 1
Bit 0 of
27
Timed function 2
Bit 1 of
28
No.
Name/Value
Description
Def/FbEq16
Bit
Value
0
Force the value of this bit to RO1, if so defined in parameter
1
Force the value of this bit to RO2, if so defined in parameter
2
Force the value of this bit to RO3, if so defined in parameter
3…15
Reserved
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...