40
ACQ550-U1 User’s Manual
Start-up, control with I/O and ID Run
How to perform the ID Run
The drive estimates motor characteristics automatically using identification
magnetization when the drive is started for the first time and after any motor
parameter (
) is changed. This is valid when parameter
ID RUN has value 0 (OFF/IDMAGN), and
•
= 1 or 2 (
VECTOR
:
SPEED
), or
•
= 3 (
SCALAR
:
FREQ
) and parameter
= 3 (
SCALAR FLYST
) or
5 (
FLY
+
BOOST
).
In most applications there is no need to perform a separate ID Run [
ID
RUN
=
1 (
ON
)]. The ID Run should be selected if:
•
vector control mode is used [parameter
= 1 or 2 (
VECTOR
:
SPEED
), and/or
•
the operation point is near zero speed, and/or
•
operation at torque range above the motor nominal torque over a wide speed
range and without any measured speed feedback is required.
Note:
If motor parameters (
) are changed after the ID
Run, it must be repeated.
ID Run procedure
The general parameter setting procedure is not repeated here. For ACQ Control
Panel see page
.
PRE-CHECK
WARNING!
The motor will run at up to approximately 50…80% of the nominal speed
during the ID Run. The motor will rotate in the forward direction.
Ensure that it is
safe to run the motor before performing the ID Run!
De-couple the motor from the driven equipment.
Check that the values of the motor data parameters
are equivalent to those on
the motor nameplate, as shown in the steps on page
If parameter values (
) are changed
before the ID Run, check that the new settings meet the following conditions:
MINIMUM
SPEED
< 0 rpm
MAXIMUM
SPEED
> 80% of the motor rated speed
MAXIMUM
CURRENT
>
I
2hd
MAX
TORQUE
1 > 50% or
MAX
TORQUE
2 > 50%, depending on which limit is in
use according to parameter
MAX
TORQUE
SEL
.
Check that the Run Enable signal is on (parameter
Ensure that the panel is in local control. Press key
to switch between HAND and AUTO
modes.
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...