36
ACQ550-U1 User’s Manual
Start-up, control with I/O and ID Run
Select EXIT to return to the listing of parameter groups.
Select the motor control mode (parameter
/
. Select EDIT to change the parameter value.
1 or 2 (
VECTOR
:
SPEED
) is available. 3 (
SCALAR
:
FREQ
) is the
default, recommended in most cases:
• for multimotor drives when the number of the motors
connected to the drive is variable
• when the nominal current of the motor is less than 20% of
the nominal current of the drive
• when the drive is used for test purposes with no motor
connected.
Press keys
/
to change the parameter value.
Select SAVE to store the modified value or select CANCEL to
leave the set mode. Any modifications not saved are cancelled.
Select EXIT to return to the listing of parameter groups.
Similarly, enter the motor data from the motor nameplate:
Note:
Set the motor data to
exactly the same value as on
the motor nameplate. For
example, if the motor nominal
speed is 1470 rpm on the
nameplate, setting the value of
parameter
MOTOR
NOM
SPEED
to 1500 rpm results in the
wrong operation of the drive.
• Motor nominal voltage (parameter
380 V
supply
voltage
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...