290
ACQ550-U1 User’s Manual
Technical data
Note:
Never mix 24 V DC and 115/230 V AC signals in the same cable.
Analog cables
Recommendations for analog signal runs:
•
Use double shielded, twisted pair cable.
•
Use one individually shielded pair for each signal.
•
Do not use a common return for different analog signals.
Digital cables
Recommendation for digital signal runs: A double shielded cable is the best
alternative, but single-shielded, twisted, multi-pair cable is also usable.
Control panel cable
If the control panel is connected to the drive with a cable, use only Category 5 Patch
ethernet cable. The maximum length that is tested to meet EMC specifications is 3 m
(9.8 ft). Longer cables are susceptible to electromagnetic noise and must be user-
tested to verify that EMC requirements are met. Where long runs are required
(especially for runs longer than about 12 m [40 ft]), use a RS232/RS485 converter at
each end and run RS485 cable.
Drive’s control connection terminals
The following table provides specifications for the drive’s control terminals
Efficiency
Approximately 98% at nominal power level.
Frame size
Control
Maximum wire size
1
Tightening torque
mm
2
AWG
N·m
lb·ft
All
1.5
16
0.4
0.3
1
Values given for solid wires.
For stranded wires, the maximum size is 1 mm
2
.
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...