ACQ550-U1 User’s Manual
269
Technical data
Ratings, 500…600 V drives
Abbreviated column headers are described in section
on page
.
Symbols
Sizing
The current ratings are the same regardless of the supply voltage within one voltage
range. To achieve the rated motor power given in the table, the rated current of the
drive must be higher than or equal to the rated motor current. Also note that:
•
the ratings apply for ambient temperature of 40 °C (104 °F)
•
the maximum allowed motor shaft power is limited to 1.5 ·
P
hd
.
If the limit is
exceeded, motor torque and current are automatically restricted. The function
protects the input bridge of the drive against overload.
In multimotor systems, the output current of the drive must be equal to or greater
than the calculated sum of the input currents of all motors.
Type
Normal use
Heavy-duty use
Frame
size
ACQ550-U1-
see below
I
2N
A
P
N
kW
P
N
hp
I
2hd
A
P
hd
kW
P
hd
hp
Three-phase supply voltage,
500
…
600 V
-02A7-6
2.8
1.5
2
2.4
1.1
1.5
R2
-03A9-6
4.0
2.2
3
2.7
1.5
2
R2
-06A1-6
6.3
4
5
3.9
2.2
3
R2
-09A0-6
9.3
5.5
7.5
6.1
4
5
R2
-011A-6
12.0
7.5
10
9.0
5.5
7.5
R2
-017A-6
18.0
11
15
11
7.5
10
R2
-022A-6
23.0
15
20
17
11
15
R3
-027A-6
28.0
18.5
25
22
15
20
R3
-032A-6
33.0
22
30
27
18.5
25
R4
-041A-6
43.0
30
40
32
22
30
R4
-052A-6
54.0
37
50
41
30
40
R4
-062A-6
64.0
45
60
52
37
50
R4
-077A-6
80.0
55
75
62
45
60
R6
-099A-6
102.0
75
100
77
55
75
R6
-125A-6
129.0
90
125
99
75
100
R6
-144A-6
149.0
110
150
125
90
125
R6
00467918.xls C
Typical ratings:
Normal use
(10% overload capability)
I
2N
continuous rms current. 10% overload is allowed for one minute in ten minutes.
P
N
typical motor power in normal use. The kilowatt power ratings apply to most IEC, 4-pole
motors. The horsepower ratings apply to most 4-pole NEMA motors.
Heavy-duty use
(50% overload capability)
I
2hd
continuous rms current. 50% overload is allowed for one minute in ten minutes.
P
hd
typical motor power in heavy duty use. The kilowatt power ratings apply to most IEC, 4-pole
motors. The horsepower ratings apply to most 4-pole NEMA motors.
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...