![ABB ACH550-UH HVAC Скачать руководство пользователя страница 52](http://html1.mh-extra.com/html/abb/ach550-uh-hvac/ach550-uh-hvac_installation-operation-and-maintenance-manual_3361774052.webp)
52
ACH550 Installation, Operation and Maintenance Manual
ACH550 E-Clipse Bypass
1. “BxR” represents both BCR and BDR.
2. Torque values shown relate to current production. Check component labels on previously installed units for required
tightening torque.
600 Volt
2
ACH550-BxR-02A7-6
R2
#8
62 in-lbs
#8
62 in-lbs
#8
7 in-lbs
#8
7 in-lbs
#6
30 in-lbs
#6
30 in-lbs
#4
35 in-lbs
#4
35 in-lbs
3
ACH550-BxR-03A9-6
R2
5
ACH550-BxR-06A1-6
R2
7.5
ACH550-BxR-09A0-6
R2
10
ACH550-BxR-011A-6
R2
15
ACH550-BxR-017A-6
R2
20
ACH550-BxR-022A-6
R3
#1
62 in-lbs
#1
62 in-lbs
#2
50 in-lbs
#2
50 in-lbs
#2
50 in-lbs
#2
50 in-lbs
25
ACH550-BxR-027A-6
R3
30
ACH550-BxR-032A-6
R4
#4
18 in-lbs
#4
18 in-lbs
#2/0
120 in-lbs
#2/0
120 in-lbs
40
ACH550-BxR-041A-6
R4
50
ACH550-BxR-052A-6
R4
#1
55 in-lbs
#1
55 in-lbs
60
ACH550-BxR-062A-6
R4
#1
75 in-lbs
#1
75 in-lbs
75
ACH550-BxR-077A-6
R6
300
MCM
274
in-lbs
300
MCM
274
in-lbs
#1/0
70 in-lbs
#1/0
70 in-lbs
#1
53 in-lbs
#1
53 in-lbs
3 x #3/0
250 in-lbs
100
ACH550-BxR-099A-6
R6
125
ACH550-BxR-125A-6
R6
300 MCM
275 in-lbs
300 MCM
275 in-lbs
250 MCM
300 in-lbs
250 MCM
300 in-lbs
#2/0
375 in-lbs
150
ACH550-Bx-R144A-6
R6
HP
Type Code
1
Base
Drive
Frame
Size
Power Wiring Data
2
Circuit
Breaker
UL Type/
NEMA
1 & 12
Circuit
Breaker
UL Type/
NEMA
3R
Disconnect
Switch
UL Type/
NEMA
1 & 12
Disconnect
Switch
UL Type/
NEMA
3R
Motor
Terminals
UL Type/
NEMA
1 & 2
Motor
Terminals
UL Type/
NEMA
3R
Ground
Lugs
UL Type/
NEMA
1 & 2
Ground
Lugs
UL Type/
NEMA
3R