ACH550 Installation, Operation and Maintenance Manual

91

ACH550-Parameter List

Complete ACH550 Drive Parameter List

GROUP 01
OPERATING DATA

101

SPEED & DIR

102

SPEED

103

OUTPUT FREQ

104

CURRENT

105

TORQUE

106

POWER

107

DC BUS VOLTAGE

109

OUTPUT VOLTAGE

110

DRIVE TEMP

111

EXTERNAL REF 1

112

EXTERNAL REF 2

113

CTRL LOCATION

114

RUN TIME (R)

115

KWH COUNTER (R)

116

APPL BLK OUTPUT

118

DI 1-3 STATUS

119

DI 4-6 STATUS

120

AI 1

121

AI 2

122

RO 1-3 STATUS

123

RO 4-6 STATUS

124

AO 1

125

AO 2

126

PID 1 OUTPUT

127

PID 2 OUTPUT

128

PID 1 SETPNT

129

PID 2 SETPNT

130

PID 1 FBK

131

PID 2 FBK

132

PID 1 DEVIATION

133

PID 2 DEVIATION

134

COMM RO WORD

135

COMM VALUE 1

136

COMM VALUE 2

137

PROCESS VAR 1

138

PROCESS VAR 2

139

PROCESS VAR 3

140

RUN TIME

141

MWH COUNTER

142

REVOLUTION 
CNTR

143

DRIVE ON TIME HI

144

DRIVE ON TIME LO

145

MOTOR TEMP

150

CB TEMP

153

MOT THERM 
STRESS

158

PID COMM VALUE 1

159

PID COMM VALUE 2

174

SAVED KWH

175

SAVED MWH

176

SAVED AMOUNT 1

177

SAVED AMOUNT 2

178

SAVED CO2

GROUP 03
FB ACTUAL SIGNALS

301

FB CMD WORD 1

302

FB CMD WORD 2

303

FB STS WORD 1

304

FB STS WORD 2

305

FAULT WORD 1

306

FAULT WORD 2

307

FAULT WORD 3

308

ALARM WORD 1

309

ALARM WORD 2

GROUP 04 
FAULT HISTORY

401

LAST FAULT

402

FAULT TIME 1

403

FAULT TIME 2

404

SPEED AT FLT

405

FREQ AT FLT

406

VOLTAGE AT FLT

407

CURRENT AT FLT

408

TORQUE AT FLT

409

STATUS AT FLT

410

DI 1-3 AT FLT

411

DI 4-6 AT FLT

412

PREVIOUS FAULT 1

413

PREVIOUS FAULT 2

GROUP 10 
START/STOP/DIR

1001

EXT1 COMMANDS

1002

EXT2 COMMANDS

1003

DIRECTION

GROUP 11 
REFERENCE SELECT

1101

KEYPAD REF SEL

1102

EXT1/EXT2 SEL

1103

REF1 SELECT

1104

REF 1 MIN

1105

REF 1 MAX

1106

REF2 SELECT

1107

REF 2 MIN

1108

REF 2 MAX

GROUP 12 
CONSTANT SPEEDS

1201

CONST SPEED SEL

1202

CONST SPEED 1

1203

CONST SPEED 2

1204

CONST SPEED 3

1205

CONST SPEED 4

1206

CONST SPEED 5

1207

CONST SPEED 6

1208

CONST SPEED 7

1209

TIMED MODE SEL

GROUP 13
ANALOG INPUTS

1301

MINIMUN AI1

1302

MAXIMUM AI1

1303

FILTER AI1

1304

MINIMUM AI2

1305

MAXIMUM AI2

1306

FILTER AI2

GROUP 14 
RELAY OUTPUTS

1401

RELAY OUTPUT 1

1402

RELAY OUTPUT 2

1403

RELAY OUTPUT 3

1404

RO 1 ON DELAY

1405

RO 1 OFF DELAY

1406

RO 2 ON DELAY

1407

RO 2 OFF DELAY

1408

RO 3 ON DELAY

1409

RO 3 OFF DELAY

1410

RELAY OUTPUT 4

1411

RELAY OUTPUT 5

1412

RELAY OUTPUT 6

1413

RO 4 ON DELAY

1414

RO 4 OFF DELAY

1415

RO 5 ON DELAY

1416

RO 5 OFF DELAY

1417

RO 6 ON DELAY

1418

RO 6 OFF DELAY

GROUP 15 
ANALOG OUTPUTS

1501

AO1 CONTENT

1502

AO1 CONTENT MIN

1503

AO1 CONTENT 
MAX

1504

MINIMUM AO1

1505

MAXIMUM AO1

1506

FILTER AO1

1507

AO2 CONTENT

1508

AO2 CONTENT MIN

1509

AO2 CONTENT 
MAX

1510

MINIMUM AO2

1511

MAXIMUM AO2

1512

FILTER AO2

GROUP 16 
SYSTEM CONTROLS

1601

RUN ENABLE

1602

PARAMETER LOCK

1603

PASS CODE

1604

FAULT RESET SEL

1605

USER PAR SET 
CHG

1606

LOCAL LOCK

1607

PARAM SAVE

1608

START ENABLE 1

1609

START ENABLE 2

1610

DISPLAY ALARMS

1611

PARAMETER VIEW

1612

FAN CONTROL

1613

FAULT RESET

GROUP 17
OVERRIDE

1701

OVERRIDE SEL

1702

OVERRIDE FREQ

1703

OVERRIDE SPEED

1704

OVERR PASS 
CODE

1705

OVERRIDE

1706

OVERRIDE DIR

1707

OVERRIDE REF

GROUP 20 
LIMITS

2001

MINIMUM SPEED

2002

MAXIMUM SPEED

2003

MAX CURRENT

2006

UNDERVOLT CTRL

2007

MINIMUM FREQ

2008

MAXIMUM FREQ

2013

MIN TORQUE SEL

2014

MAX TORQUE SEL

2015

MIN TORQUE 1

2016

MIN TORQUE 2

2017

MAX TORQUE 1

2018

MAX TORQUE 2

GROUP 21 
START/STOP

2101

START FUNCTION

2102

STOP FUNCTION

2103

DC MAGN TIME

2104

DC HOLD CTL

2105

DC HOLD SPEED

2106

DC CURR REF

2107

DC BRAKE TIME

2108

START INHIBIT

2109

EM STOP SEL

2110

TORQ BOOST 
CURR

2113

START DELAY

GROUP 22 
ACCEL/DECEL

2201

ACC/DEC 1/2 SEL

2202

ACCELER TIME 1

2203

DECELER TIME 1

2204

RAMP SHAPE 1

2205

ACCELER TIME 2

2206

DECELER TIME 2

2207

RAMP SHAPE 2

2208

EM DEC TIME

2209

RAMP INPUT 0

GROUP 23 
SPEED CONTROL

2301

PROP GAIN

2302

INTEGRATION TIME

2303

DERIVATION TIME

2304

ACC 
COMPENSATION

2305

AUTOTUNE RUN

GROUP 25
CRITICAL SPEEDS

2501

CRIT SPEED SEL

2502

CRIT SPEED 1 LO

2503

CRIT SPEED 1 HI

2504

CRIT SPEED 2 LO

2505

CRIT SPEED 2 HI

2506

CRIT SPEED 3 LO

2507

CRIT SPEED 3 HI

GROUP 26 
MOTOR CONTROL

2601

FLUX OPT ENABLE

2602

FLUX BRAKING

2603

IR COMP VOLT

2604

IR COMP FREQ

2605

U/F RATIO

2606

SWITCHING FREQ

2607

SW FREQ CTRL

2608

SLIP COMP RATIO

2609

NOISE 
SMOOTHING

2619

DC STABILIZER

2625

OVERMODULATION

GROUP 29 
MAINTENANCE TRIG

2901

COOLING FAN 
TRIG

2902

COOLING FAN ACT

2903

REVOLUTION TRIG

2904

REVOLUTION ACT

2905

RUN TIME TRIG

2906

RUN TIME ACT

2907

USER MWH TRIG

2908

USER MWH ACT

GROUP 30 
FAULT FUNCTIONS

3001

AI<MIN FUNCTION

3002

PANEL COMM ERR

3003

EXTERNAL FAULT 1

3004

EXTERNAL FAULT 2

3005

MOT THERM PROT

3006

MOT THERM TIME

3007

MOT LOAD CURVE

3008

ZERO SPEED LOAD

3009

BREAK POINT 
FREQ

3010

STALL FUNCTION

3011

STALL 
FREQUENCY

3012

STALL TIME

3017

EARTH FAULT

3018

COMM FAULT 
FUNC

3019

COMM FAULT TIME

3021

AI1 FAULT LIMIT

3022

AI2 FAULT LIMIT

3023

WIRING FAULT

3024

CB TEMP FAULT

3028

EARTH FAULT LVL

GROUP 31 
AUTOMATIC RESET

3101

NR OF TRIALS

3102

TRIAL TIME

3103

DELAY TIME

3104

AR OVERCURRENT

3105

AR OVERVOLTAGE

3106

AR 
UNDERVOLTAGE

3107

AR AI<MIN

3108

AR EXTERNAL FLT

GROUP 32 
SUPERVISION

3201

SUPERV 1 PARAM

3202

SUPERV 1 LIM LO

3203

SUPERV 1 LIM HI

3204

SUPERV 2 PARAM

3205

SUPERV 2 LIM LO

3206

SUPERV 2 LIM HI

3207

SUPERV 3 PARAM

3208

SUPERV 3 LIM LO

3209

SUPERV 3 LIM HI

GROUP 33 
INFORMATION

3301

FW VERSION

3302

LP VERSION

3303

TEST DATE

3304

DRIVE RATING

3305

PARTABLE 
VERSION

GROUP 34 
PANEL DISPLAY

3401

SIGNAL 1 PARAM

3402

SIGNAL 1 MIN

3403

SIGNAL 1 MAX

3404

OUTPUT 1 DSP 
FORM

3405

OUTPUT 1 UNIT

3406

OUTPUT 1 MIN

3407

OUTPUT 1 MAX

3408

SIGNAL 2 PARAM

3409

SIGNAL 2 MIN

3410

SIGNAL 2 MAX

3411

OUTPUT 2 DSP 
FORM

3412

OUTPUT 2 UNIT

3413

OUTPUT 2 MIN

3414

OUTPUT 2 MAX

3415

SIGNAL 3 PARAM

3416

SIGNAL 3 MIN

3417

SIGNAL 3 MAX

3418

OUTPUT 3 DSP 
FORM

3419

OUTPUT 3 UNIT

3420

OUTPUT 3 MIN

3421

OUTPUT 3 MAX

GROUP 35 
MOTOR TEMP MEAS

3501

SENSOR TYPE

3502

INPUT SELECTION

3503

ALARM LIMIT

3504

FAULT LIMIT

GROUP 36 
TIMED FUNCTIONS

3601

TIMERS ENABLE

3602

START TIME 1

3603

STOP TIME 1

3604

START DAY 1

3605

STOP DAY 1

3606

START TIME 2

3607

STOP TIME 2

3608

START DAY 2

3609

STOP DAY 2

3610

START TIME 3

3611

STOP TIME 3

3612

START DAY 3

3613

STOP DAY 3

3614

START TIME 4

3615

STOP TIME 4

3616

START DAY 4

3617

STOP DAY 4

3622

BOOST SEL

3623

BOOST TIME

3626

TIMER 1 SRC

3627

TIMER 2 SRC

3628

TIMER 3 SRC

3629

TIMER 4 SRC

GROUP 37 
USER LOAD CURVE

3701

USER LOAD C 
MODE

3702

USER LOAD C 
FUNC

3703

USER LOAD C TIME

3704

LOAD FREQ 1

3705

LOAD TORQ LOW 1

3706

LOAD TORQ HIGH 1

3707

LOAD FREQ 2

3708

LOAD TORQ LOW 2

3709

LOAD TORQ HIGH 2

3710

LOAD FREQ 3

3711

LOAD TORQ LOW 3

3712

LOAD TORQ HIGH 3

3713

LOAD FREQ 4

3714

LOAD TORQ LOW 4

3715

LOAD TORQ HIGH 4

3716

LOAD FREQ 5

3717

LOAD TORQ LOW 5

3718

LOAD TORQ HIGH 5

GROUP 40 
PROCESS PID SET 1

4001

GAIN

4002

INTEGRATION TIME

4003

DERIVATION TIME

4004

PID DERIV FILTER

4005

ERROR VALUE INV

4006

UNITS

4007

DSP FORMAT

4008

0% VALUE

4009

100% VALUE

4010

SET POINT SEL

4011

INTERNAL SETPNT

4012

SETPOINT MIN 

4013

SETPOINT MAX

4014

FBK SEL

4015

FBK MULTIPLIER

4016

ACT1 INPUT

4017

ACT2 INPUT

4018

ACT1 MINIMUM

4019

ACT1 MAXIMUM

4020

ACT2 MINIMUM

4021

ACT2 MAXIMUM

4022

SLEEP SELECTION

4023

PID SLEEP LEVEL

4024

PID SLEEP DELAY

4025

WAKE-UP DEV

4026

WAKE-UP DELAY

4027

PID 1 PARAM SET

GROUP 41 
PROCESS PID SET 2

4101

GAIN

4102

INTEGRATION TIME

4103

DERIVATION TIME

4104

PID DERIV FILTER

4105

ERROR VALUE INV

4106

UNITS

4107

UNIT SCALE

4108

0% VALUE

4109

100% VALUE

4110

SET POINT SEL

4111

INTERNAL SETPNT

4112

SETPOINT MIN 

4113

SETPOINT MAX

4114

FBK SEL

4115

FBK MULTIPLIER

4116

ACT1 INPUT

Содержание ACH550 series

Страница 1: ...ACH550 Installation Operation and Maintenance Manual I O M ACH550 UH HVAC Drives 1 550 HP ACH550 BCR BDR VCR VDR E Clipse Bypass Drives 1 400 HP ACH550 PCR PDR Packaged Drives with Disconnect 1 550 HP...

Страница 2: ...es on the terminals of the relay outputs WARNING When the control terminals of two or more drives are connected in parallel the auxiliary voltage for these control connections must be taken from a sin...

Страница 3: ...ial number label attached on upper part of the chokeplate between the mounting holes Type code label attached on the heat sink on the side of the enclosure S N ACH550 UH 059A 2 2030700001 SW V 2 06B 2...

Страница 4: ...with Input Disconnect is connected to the line Disconnect and lock out power to the drive before servicing the drive Failure to disconnect power may cause serious injury or death 1 Install wiring WARN...

Страница 5: ...Disconnect Switch or Circuit Breaker Motor Terminals Gnd UL Type NEMA 1 12 UL Type NEMA 1 12 Enclosures Enclosures Input Power Terminals I O Conduit Bottom I O Conduit Top Vertical Construction Hinged...

Страница 6: ...floor mounted Floor mounted UL Type NEMA 1 12 Drive with Input Disconnect units are configured for wiring access from the top and include a removable conduit mounting plate The following figure shows...

Страница 7: ...on disconnect switches for the following rated ACH550 PDR products is 7 in lbs Do not use a power driver or over tighten to prevent breaking screw heads or stripping the terminal 230 VAC 460 VAC 600...

Страница 8: ...ine power Failure to disconnect line power could result in death or serious injury Note For the remainder of the wiring motor and control wiring refer to page 7 Input Power UL Type NEMA 3R Enclosures...

Страница 9: ...10 7 in lbs 10 7 in lbs Refer to Drive s power connection terminals 10 35 in lbs 10 35 in lbs 1 5 ACH550 PxR 06A6 2 R1 2 ACH550 PxR 07A5 2 R1 3 ACH550 PxR 012A 2 R1 5 ACH550 PxR 017A 2 R1 7 5 ACH550 P...

Страница 10: ...in lbs 6 35 in lbs 15 ACH550 PxR 023A 4 R2 20 ACH550 PxR 031A 4 R3 3 50 in lbs 3 50 in lbs 3 50 in lbs 3 50 in lbs 25 ACH550 PxR 038A 4 R3 4 18 in lbs 4 18 in lbs 30 ACH550 PxR 045A 4 R3 40 ACH550 Px...

Страница 11: ...in lbs 8 7 in lbs Refer to Drive s power connection terminals 6 35 in lbs 6 35 in lbs 3 ACH550 PxR 03A9 6 R2 5 ACH550 PxR 06A1 6 R2 7 5 ACH550 PxR 09A0 6 R2 10 ACH550 PxR 011A 6 R2 15 ACH550 PxR 017A...

Страница 12: ...ut Disconnect is an ACH550 AC adjustable frequency drive packaged with an input disconnect switch or circuit breaker and with a door interlocked external operating handle The operating handle can be p...

Страница 13: ...rd configurations and identifies the major components Operating Handle ACH550 Drive for Disconnect Switch or Circuit Breaker UL Type NEMA 1 12 UL Type NEMA 1 12 UL Type NEMA 1 12 Floor Mount UL Type N...

Страница 14: ...ation Interval Instruction Check replace hinged door wall mount enclosure inlet air filter Hinged door wall mount UL Type NEMA 12 enclosures Check every 3 months Replace as needed Enclosure air filter...

Страница 15: ...t the hooks catch on the enclosure 6 Replace the mounting screw Tighten until the gasket on the bracket is about 50 compressed Enclosure air filter replacement UL Type NEMA 12 floor mount enclosures F...

Страница 16: ...07 RAMP SHAPE 2 2208 EM DEC TIME 2209 RAMP INPUT 0 GROUP 23 SPEED CONTROL 2301 PROP GAIN 2302 INTEGRATION TIME 2303 DERIVATION TIME 2304 ACC COMPENSATION 2305 AUTOTUNE RUN GROUP 25 CRITICAL SPEEDS 250...

Страница 17: ...1 LAST FAULT 0402 F1 TIME 1 0403 F1 TIME 2 0404 F1 VOLTAGE 0405 F1 CURRENT 0406 F1 EVENT 1 0407 F1 E1 TIME 0408 F1 EVENT 2 0409 F1 E2 TIME 0410 FAULT 2 0411 F2 TIME 1 0412 F2 TIME 2 0413 F2 VOLTAGE 04...

Страница 18: ...94 ACH550 Installation Operation and Maintenance Manual 3AUA0000081824 REV C Effective 12 01 2014 Supersedes 04 15 2012 ABB Inc...

Отзывы: