ACH550-UH User’s Manual
1-91
Parameters
Group 04: FAULT HISTORY
This group stores a recent history of the faults reported by the drive.
Group 04: Fault History
Code Description Range
Resolution
Default
S
0401
LAST FAULT
Fault codes
1
0
(panel displays as text)
0 – Clear the fault history (on panel = NO RECORD).
n – Fault code of the last recorded fault. The fault code is displayed as a name. See section
for the fault codes and names. The fault name shown for this parameter may be shorter than the
corresponding name in the fault listing, which shows the names as they are shown in the fault display.
0402
FAULT TIME 1
Date dd.mm.yy /
1 day
0
power-on time in days
The day on which the last fault occurred. Either as:
• A date – if real time clock is operating.
• The number of days after power on – if real time clock is not used, or was not set.
0403
FAULT TIME 2
Time hh:mm:ss
2 s
0
The time at which the last fault occurred. Either as:
• Real time, in format hh:mm:ss – if real time clock is operating.
• The time since power on (minus the whole days reported in 0402), in format hh:mm:ss – if real time clock is not
used, or was not set.
• Format on the Basic Control Panel: The time since power on in 2-second ticks (minus the whole days reported in
0402). 30 ticks = 60 seconds. E.g. Value 514 equals 17 minutes and 8 seconds (= 514/30).
0404
SPEED AT FLT
-32768…+32767
1 rpm
0
The motor speed (rpm) at the time the last fault occurred.
0405
FREQ AT FLT
-3276.8…+3276.7
0.1 Hz
0
The frequency (Hz) at the time the last fault occurred.
0406
VOLTAGE AT FLT
0.0…6553.5
0.1 V
0
The DC bus voltage (V) at the time the last fault occurred.
0407
CURRENT AT FLT
0.0…6553.5
0.1 A
0
The motor current (A) at the time the last fault occurred.
0408
TORQUE AT FLT
-3276.8…+3276.7
0.1%
0
The motor torque (%) at the time the last fault occurred.
0409
STATUS AT FLT
0000…FFFF hex
1
0
The drive status (hex code word) at the time the last fault occurred.
0410
DI 1-3 AT FLT
000…111
1
0
(0…7 decimal)
The status of digital inputs 1…3 at the time the last fault occurred.
0411
DI 4-6 AT FLT
000…111
1
0
(0…7 decimal)
The status of digital inputs 4…6 at the time the last fault occurred.
0412
PREVIOUS FAULT 1
As par. 0401
1
0
Fault code of the second last fault. Read-only.
0413
PREVIOUS FAULT 2
As par. 0401
1
0
Fault code of the third last fault. Read-only.
Содержание ACH550-BCR
Страница 4: ...iv Manual contents ...
Страница 5: ...ACH550 UH User s Manual 1 1 ACH550 UH HVAC Drives 1 550 HP User s Manual 2016 ABB All Rights Reserved ...
Страница 6: ......
Страница 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Страница 36: ...1 32 ACH550 UH User s Manual Installation ...
Страница 70: ...1 66 ACH550 UH User s Manual Application macros ...
Страница 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Страница 348: ......
Страница 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Страница 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Страница 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Страница 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Страница 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Страница 608: ......
Страница 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Страница 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Страница 641: ......