Chapter 5 – Commissioning the Drive Section
ACS 600 MultiDrive
5-3
Connecting Voltage to
Auxiliary Circuits
The table below describes how to connect voltage to the Supply
Section input terminals and to the Auxiliary Control Unit (ACU) for the
first time.
Action
Information
WARNING!
When voltage is connected to the input terminals of the Supply Section,
the voltage will also be connected to the Auxiliary Control Unit and to auxiliary circuits
- also to the ones wired to drive sections.
Make sure that it is safe to connect voltage to the input terminals. Ensure that while
the voltage is connected:
• Nobody is working on the unit or circuits that are wired from outside into the
cabinets.
• The cabinet doors are closed.
Disconnect the 230 VAC cables that lead from the terminal
blocks to the outside of the equipment and have not yet
been checked, and the connections which may not yet have
been completed.
Disconnect the communication link to the overriding system
by removing the fiber optic cables.
See the circuit diagrams
delivered with the device.
Make sure that the main contactor/air circuit breaker cannot
be closed inadvertently by remote control, e.g. by
temporarily opening a connection in its control circuit.
Be ready to trip the main breaker of the supply transformer
in case something abnormal occurs.
Ensure that all cabinet doors are closed.
Close the main breaker of the supply transformer.
Frame sizes B1, B2, B3 and B4 type ACA 631-0850-61-xx:
Close the main disconnecting switch of the Supply Section.
~
=
~
=
~
=
Auxiliary
voltage
Содержание ACA 6 Series
Страница 4: ......
Страница 8: ...Safety Instructions vi ACS 600 MultiDrive ...
Страница 12: ...x ACS 600 MultiDrive Hardware Manual ...
Страница 26: ...Chapter 1 Introduction 1 14 ACS 600 MultiDrive Hardware Manual ...
Страница 42: ...Chapter 2 Mechanical Installation 2 16 ACA 6xx Sections and ACS ACC 6x7 132 to 3000 kW Frequency Converters ...
Страница 100: ...Chapter 6 Preventive Maintenance 6 6 ACS 600 MultiDrive ...
Страница 101: ......