Description
Section 3 Parameter Interface
32
3BSE042835-600
Type Description Keyword
The description field can hold a keyword before the actual description. This
keyword holds information about its usage for the application engineer. All
parameters in Control Module types, Diagram types, and IN_OUT parameters
should have at least one of the first four comments in
.
For Function Block Types parameters only the comments related to EDIT and
NONSIL are applicable.
For control modules, it is very important that the IN and OUT markings of
parameters are correct. The application programmer needs this information to avoid
program loops and to know which parameters to write to and read from,
respectively.
The parameters are shown as IN, OUT, or INOUT ports in Function Designer
dependent of the first characters in the parameter description:
Table 4. Type Description Keywords
Keyword
Description
IN
The parameter is only read.
OUT
The parameter is only written.
IN(OUT)
The parameter is both read and written, but mostly read.
OUT(IN)
The parameter is both read and written, but mostly written.
NODE
Used when the parameter has a graphical connection node (control
modules only).
EDIT
The value of the parameter is used the first execution after transition
from Edit to Run mode without initialization. Cannot be changed online.
NONSIL
The output parameter marked with NONSIL originates from a restricted
marked sub-object and is not allowed to be used in the critical loop. If
the object is set to SIL1-2 or SIL3, but the parameters are Non-SIL,
then it is possible to obtain partial functionality in the SIL environment.
DEFAULT The output parameters on SIL marked object where the information
originates from restricted sub objects.
Содержание AC 800M
Страница 1: ...Power and productivity for a better worldTM AC 800M Library Object Style Guide System Version 6 0...
Страница 2: ......
Страница 3: ...AC 800M Library Object Style Guide System Version 6 0...
Страница 12: ...Related Documentation About This User Manual 12 3BSE042835 600...
Страница 18: ...Naming Convention Section 1 Libraries 18 3BSE042835 600...
Страница 108: ...SIL Mark Restrictions Section 6 Program Code Issues 108 3BSE042835 600...
Страница 116: ...Standard Library Parameters Appendix A Names and Abbreviations 116 3BSE042835 600...
Страница 119: ......