1.5.2.4
Addressing
In the following, the information in the "Type" column refers to the data type designation of the
Automation Builder (see AC31 system data
Chapter 1.3 “System data and CS31 bus system
). The information in the "Type" column must be interpreted from the viewpoint
of the CS31 bus master. The information in brackets must be interpreted from the viewpoint of
the replacement device (CS31 bus slave).
Table 43: CS31 bus (32 inputs / 32 outputs)
Byte
Type
Bit
Connector / Terminal
1
8 bit input (send)
0 ... 7
X2 / 1.0 ... 1.7
2
8 bit input (send)
0 ... 7
X3 / 2.0 to 2.7
3
8 bit input (send)
0 ... 7
X5 / 3.0 to 3.7
4
8 bit input (send)
0 ... 7
X6 / 4.0 to 4.7
5
8 bit output (receive)
0 ... 7
X2 / 1.0 ... 1.7
6
8 bit output (receive)
0 ... 7
X3 / 2.0 to 2.7
7
8 bit output (receive)
0 ... 7
X5 / 3.0 to 3.7
8
8 bit output (receive)
0 ... 7
X6 / 4.0 to 4.7
Table 44: CS31 bus (32 outputs)
Byte
Type
Bit
Connector / Terminal
1
8 bit output (receive)
0 ... 7
X2 / 1.0 ... 1.7
2
8 bit output (receive)
0 ... 7
X3 / 2.0 to 2.7
3
8 bit output (receive)
0 ... 7
X5 / 3.0 to 3.7
4
8 bit output (receive)
0 ... 7
X6 / 4.0 to 4.7
NOTICE!
In case of overloading or a short-circuit, the output limits the electricity and
switches off thermally. The LED of the overloaded output is also switched off
and the corresponding error indication of the DO524 flashes.
1.5.2.5
I/O configuration
The existing device had a DIP switch on the upper printed circuit board. Since the replacement
device is not equipped with an upper printed circuit board, the DIP switch is arranged on the
lower printed circuit board instead.
AC31 Adapters
Replacement devices: I/O modules > Replacement device 07DC92-AD
2018/09/24
3ADR010122, 8, en_US
78