![ABB 88TK50-E/R1210 Скачать руководство пользователя страница 12](http://html.mh-extra.com/html/abb/88tk50-e-r1210/88tk50-e-r1210_module-and-application-description_2506012.webp)
88TK50/R1210
12
S = Static annunciations disappear automatically upon deactivation
D = Dynamic annunciations are cancelled after the contents of the diagnosis register has been transmitted
0 = Not used
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Type
0
0
0
0
0
0
0
D
D
D
D
D
D
D
D
diagnosis register
0
Background
Module address (decimal) of disconnected module
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Type
0
0
0
0
0
0
0
0
0
0
S
0
S
S
S
diagnosis register
Wrong station / system address setting
Wrong module address setting 60, 61
0
Background
Hardware defect
Discrepancy of operating mode setting
136:
Cause for ’Module from AS bus disconnected’ (62/246/8)
when module address 60 is set
152:
Cause for ’Module from AS bus disconnected’ (62/246/8)
when module address 61 is set
139:
Cause for ’Partner module fault’ (62/246/11)
when module address 60 is set
155:
Cause for ’Partner module fault’ (62/246/11)
when module address 61 is set
Figure 5: Background diagnosis registers 136, 139, 152 and 155 are read using module address 62.