background image

CHAPTER 4 - Start-up and adjustment of the drive 

 

MANIU04.9607 GB 03/97

 

Page 4.16

 

 

alarm:  the  convertor  remains  enabled,  but  with  maximum  current  equal  to  the  motor  rated 
current, set with 

P18, IN_MOT

On the other side, to protect the motor, besides the rated current of the motor, it is necessary 
to  set  also  the  thermal  time  constant,  with  the  parameter 

P19,  TH_MOT, 

expressed  in 

seconds. In this way, if higher current than the rated current of the motor, but lower than the 
rated current of the convertor (that could be delivered indefinitely) is required in steady-state, 
the I

2

t alarm for the motor protection intervenes. The drive remains enabled, but the maximum 

current limit is set in relation to the rated current of the motor. 
In  both  cases,  the  I

2

t  alarm  will  be  visualized  both  on  the  7-segment  display  and  on  the 

keyboard. 
To  reset  the  drive  to  normal  conditions,  it  is  necessary  to  reset  the  alarm,  once  its  possible 
cause has been removed. 
 

4.5.3 Speed mode 

 

4.5.3.1 Adjusting of PI controller 

 

The drive uses a PI algorithm for speed mode. It is therefore necessary to set the dynamics of 
controller through parameters 

P1, KP,

 that represents the proportional gain of controller, and 

P2, KI,

 that represents the integral gain. 

Basically,  it  can  be  said  that  when  stepping  up  both  gains,  it  is  possible  to  increase  the 
transient  response  of  the  motor  to  the  reference  changes  and  to  noises.  This  will  however 
also decrease the system stability margin. Moreover, the relation KP/KI,

 

that sets the zero of 

the PI regulator, is also important for good control and stability. When increasing the KI

 

gain, 

the  drive  capability  to  maintain  the  motor  stopped  in  one  position,  delivering  torque,  is 
increased. 
However, it is necessary to adjust the dynamic characteristics of the system convertor-motor 
to  the  mechanical system in which it is used. Therefore, we advise to adopt such values for 
KP  and  KI  as  to  guarantee  a  good  compromise  between  dynamic  performances  and  noise 
sensitivity. 
As well as with analog reference, the speed command can be set directly with the keyboard. 
At start up, this is the default condition. 
 

4.5.3.2 Speed analog reference: offset adjusting 

 

The speed analog reference is drawn from the differential input related to the terminals 

+RIF 

(J1/7)  and  -RIF  (J1/8). 

It can be enabled with the keyboard through the flag

 F2, Reference 

from potentiometer, 

through serial interface or with one of the two configurable inputs. 

The reference enabling input (terminal SE, J1/4) can be used as START/STOP command: its 
function is setting the reference to zero when it is disabled. 
To  use  the  speed  analog  reference  it  is  necessary  to  calibrate  the  offset  of  12-bit  A/D 
converter: this procedure is totally automatic and can be carried out by setting flag

 F13, A/D 

Converter  tuning, 

which  will  determine  the  value  of  parameters 

P20,  OFF_AN 

and 

P21, 

OFFMED. 

To adjust the offset, put a 0V value between the two RIF and -RIF, enable the speed 
reference (SE=H) and set the flag F2: at this moment set also the flag F13, to start the offset 
adjusting.  The  procedure  stops  when  the  keyboard  shows  the  word 

DONE, 

in 

correspondence  with  F13.    Now  it  is  possible  to  drive  the  convertor  in  speed  mode  with  
analog reference. 

NOTE:

 lf the offset adjustment is not satisfactory (with 0V reference the motor turns slowly) it 

is possible to repeat the procedure with torque enabled (terminal 

RE, J1/3

): if the adjusting is 

still  not  satisfactory,  it  is  possible  to  intervene  and  directly  modify  the  parameter  P21, 
increasing or decreasing the value to correct the motor performances. 

 

Содержание 8 Series

Страница 1: ...s servomotors SERIES 8 and digital convertors BHL D In conformity with EEC Directives and mark Use and installation manual Ref MAN1U04 9607 GB Updating 02 Edition March 1997 ABB Servomotors S r l ABB ABB Servomotors S r l ...

Страница 2: ... Servomotors S r l Asti Printed in Italy This document contains confidential information belonging to ABB Servomotors S r l When accepting this document the receiver commits himself not to reproduce copy with any system transmit to third parties the document itself and the information therein contained as a whole or partially and not to allow anyone else for no reason to proceed as described above...

Страница 3: ...ves and matching servomotor convertor CHAPTER 3 INSTALLATION OF THE DRIVE 3 1 Installation of convertors BHL D 3 2 Installation of servomotors SERIES 8 3 3 Guidelines on the application of electromagnetic compatibility 3 4 References to safety regulations CHAPTER 4 START UP AND ADJUSTMENT OF THE DRIVE 4 1 Introduction 4 2 How to use the keyboard 4 3 External connections 4 4 Indications for connect...

Страница 4: ...uments cited in paragraph 1 3 1 2 1 EMC Electro Magnetic Compatibility the capability of a device an apparatus or of a system to function in its electromagnetic environment satisfactorily without introducing electromagnetic disturbances not acceptable for what is placed in that environment in practice this expression includes all requirements both of emission disturbances provoked by the apparatus...

Страница 5: ...CHAPTER 1 INTRODUCTION MANIU04 9607 GB 03 97 Page 1 2 Fig 1 1 ...

Страница 6: ...s a single commercial unit 1 2 8 INSTALLATION union made up of several apparatus and or systems combined together so as to obtain a specific aim but not destined to be put on the market as a single commercial unit 1 2 9 COMPONENT element used for the realization of an apparatus but that cannot be regarded as an apparatus itself since it has no intrinsic function for the end user Simple components ...

Страница 7: ...ences in the text are in square brackets 1 3 1 Electro Magnetic Compatibility Directive 1 Community Directive 89 336 EEC dtd 3 May 1989 related to Electro Magnetic Compatibility and following modifications 92 31 EEC and 93 68 EEC 2 Italian Decree Law 4 December 1992 n 476 Actuation of the directive 89 336 EEC of the Council on 3 May 1989 on the approximation of the laws of the member states relati...

Страница 8: ...tion 1 general directives 1 4 Compliance with the EMC Directives and mark 1 4 1 Conditions for the compliance with the EMC directives of the drives made up of servomotors SERIES 8 and convertors SERIES BHL D The compliance of the drives defined in the title of this paragraphwith directives 1 2 3 on Electro Magnetic Compatibility is valid only under the conditions listed below 1 4 1 1 Drives define...

Страница 9: ...e the manufacturer s declaration also known as Declaration of Incorporation Manufacturer s Declaration In order to comply with the Machine Directive MD 89 392 EEC and further amendments ABB Servomotors declares that drives made up of servomotors SERIES 8 and convertors series BHL D must be installed according to its instructions and must not be started up until the machinery into which they are to...

Страница 10: ...o our Customer Service in order to make as quick as possible the diagnostics of the fault and its elimination Therefore except for some special cases the repairs foresees the intervention of specialized personnel 1 6 2 Servomotor plate 1 6 3 Convertor plate ABB Servomotors S r l MADE IN ITALY TYPE _________________________________________ S N _____________ PART NUMBER _____________________________...

Страница 11: ..._____ FACT HW LEV ____________ D S LAST HW HW HW HW HW D D D 0 INSTAL S s s Is FACT SW LEV ____________ D S LAST SW SW SW SW SW D D D D INSTAL S S S S 1 6 4 Customer Service Address your requests for details service or spare parts to ABB Servomotors S r l Customer Service Frazione Stazione Portaconiaro 97 C I 14100 ASTI ITALY Telephone 39 141 476 456 Telefax 39 141 296 455 ...

Страница 12: ...d 6000 RPM Table 2 1 contains some data concerning servomotors of this series complete data regarding dimensions mechanical and electrical characteristics and performances of these servomotors can be found in the catalogue 3AT K 93056 R004 ED 2 96 that can be supplied on request in the following pages of this manual we will refer to this publication as the Catalogue Table 2 1 Servomotor Type SERIE...

Страница 13: ...3 6204 2ZR C3 950 750 575 475 20 865 1500 3000 6207 2ZR C3 6205 2ZR C3 1750 1400 1000 850 2715 Notes 1 Values for simultaneous axial and radial stresses are available on request 2 Values for versions with integrated brake special versions are available on request 3 Values for admissible axial loads are valid for force direction FA towards the motor for the opposite direction a reduction is necessa...

Страница 14: ...0 optional RBextra W Switching frequency kHz 5 5 5 5 10 10 10 Speed range 0 6000 RPM fmax 300Hz Position transducer 2 pole resolver Resolver motor phase adjustment Automatic procedure Speed reference input 10V input impedance 200kΩ differential Current reference input 10V input impedance 24 kΩ Torque analog limit circuit input 0 10V input impedance 24 kΩ Input for enabling commands Galvanically in...

Страница 15: ... 27 7 28 865 2 15 14 28 21 0 48 2 48 2 28 865 230 18 36 19 4 38 9 38 9 36 865 2 30 25 50 21 0 54 40 2 50 865 3 15 14 28 27 1 54 54 28 865 3 30 35 70 29 0 67 9 67 9 70 865 4 15 18 36 36 0 72 72 36 865 4 15 25 50 37 0 100 100 50 865 4 30 35 70 37 0 77 7 77 7 70 Legend T0 Continuous stall torque Tmax Peak stall torque TNmax Peak torque at nominal speed Imax Motor current at Tmax The maximum current o...

Страница 16: ...d in a vertical position The distance equal to 150 mm indicated above and below in Fig 3 1 is the room that must be left free for air flow this is valid both for size 223 and for size 224 Do not stop the flow of cooling air with external bodies placed too close to the convertor see minimum distances described in the figure Do not place the drive near heat sources Fig 3 1 ...

Страница 17: ...CHAPTER 3 Installation of the drive MANIU04 9607 GB 03 97 Page 3 2 3 1 2 Dimensions SIZE 223 Models from 5 10 to 18 36 Fig 3 2 ...

Страница 18: ...CHAPTER 3 Installation of the drive MANIU04 9607 GB 03 97 Page 3 3 SIZE 224 Models 25 50 Fig 3 3 ...

Страница 19: ... 3 Installation of the drive MANIU04 9607 GB 03 97 Page 3 4 SIZE 224 Models 35 70 and 50 100 Fig 3 4 3 1 3 Electrical installation As regards power and signal connections please refer to paragraphs 4 3 and 4 4 ...

Страница 20: ...nge mounted with passing holes on the flange vertical shaft down IMV3 flange mounted with passing holes on the flange vertical shaft up lMB14 flange mounted with blind tapped holes on the flange horizontal lMV18 flange mounted with blind tapped holes on the flange vertical shaft down lMV19 flange mounted with blind tapped holes on the flange vertical shaft up 3 2 1 3 Pulleys and couplings Coupling...

Страница 21: ...ed with A Fig 3 6 must not be connected CAUTION It is necessary to respect the correspondence of the connections between motor and convertor without fail A mistake in phase connection will not make drive operation possible The yellow green connection cable between the ground of the motor and the ground of the convertor must be connected to the terminal marked with the symbol For these connections ...

Страница 22: ...CHAPTER 3 Installation of the drive MANIU04 9607 GB 03 97 Page 3 7 Extra M5 hole available outside the connection box Fig 3 5 ...

Страница 23: ...CHAPTER 3 Installation of the drive MANIU04 9607 GB 03 97 Page 3 8 Extra M5 hole available outside the connection box Fig 3 6 ...

Страница 24: ...mally used in connection with the convertor see paragraph 4 3 5 It can be used for example in special cases as signaling in possible circuits of plant supervision connected to a system PLC The contact can work at 220 Vac with a current up to 5 A 3 2 2 4 Brake connections only if this option exists When the brake option is present connections must be made according to the following instructions WAR...

Страница 25: ...nces irradiated disturbances 30 MHz 1000 MHz 3 3 5 Industrial experience has demonstrated that the main causes of lack of compatibility are due to condueted disturbances 3 3 6 The installation of the drive must be executed scrupulously following the instructions contained in the paragraphs 3 1 and 3 2 of this chapter 3 3 7 In view of electromagnetic compatibility the installation must be carried o...

Страница 26: ...on the line input of some convertors 3 3 8 4 Cable shieldings must stop as nearer as possible the terminal board if the connection of the shield to a mass or in some cases to ground is prescribed it must be carried out with the shortest possible connections and with conductors with an adequate section 3 3 8 5 lt is important that all panels within the electric board are connected with mechanical c...

Страница 27: ...both cabin side and motor side ground connoctions must be of adequate section and very short This is an EMC specific requirement which can apparently in contrast with what often prescribed i e the opportunity to connect shields to ground on one side only this prescription requires very efficient grounds 3 4 External ballast resistors When the ballast resistor is external this must be assembled in ...

Страница 28: ...on the dc intermediate circuit and on the associated circuits A proper warning placed visibly must be present on the BHL D convertor to warn about this danger according to what established in EN 60204 1 6 2 3 3 5 3 Supply sectioning device WARNING Since the BHL D convertor is prepared to be put in an electric cabin possibly also containing other apparatus the supply sectioning device manually cont...

Страница 29: ...Servomotors series 8 have IP 55 protection degree BHL D convertors have IP20 protection degree to fulfill what prescribed in 4 4 5 Contaminating elements of the standard EN 60204 1 they must care of the manufacturer of the machine be put into an adequate case electric cabin according to the required protection degree ...

Страница 30: ...ted with a flat cable in the appropriate connector The keyboard management is arranged in three visualizstion windows each one with a different function the first window the window of References is shown when the unit is switched on The second window shown is for Parameters and the third one contains Flags To move from one window to another use MODE key The first window shows all references of spe...

Страница 31: ...TC or NTC are visualized whether it is set or not Flags can be grouped in two different types procedure flags and configuration flags The former are used to generate a particular sequence of actions that will then bring the drive back to start condition usually these are autoadjusting or autotuning procedures In general they are CLEAR type flags lf first ENTER the cursor appears and then the arrow...

Страница 32: ...t when the motor is controlled in torque mode The settable value changes from 200 0 In to 200 0 In in relation to the rated current of the drive the value that can be set is limited by parameter P5 I_MAX that represents the maximum absolute value of current always referred to the rated current On the contrary if instead of considering this parameter as current limit analog current limit is used th...

Страница 33: ...h the analog output DAC2 to return within the allowed limits or to increase the resolution within a given range In other words it is the scaling factor between the numerical value and the analog value of the internal variable to be visualized On defauft configuration OUT1_A 4 actual speed monitor and OUT2_A 5 torque signal monitor are set already normalized according to the maximum values set with...

Страница 34: ...der pulse width at 256 pulse per revolution value equal to 9 lf for the external control it is enough to detect a rising or falling wave front it is not necessary to specify it P38 SER_ID Internal parameter not to be modified except if serial communication is used 4 2 3 Description of flags window This window shows all the flags that it is possible to set either configuration flags or procedure fl...

Страница 35: ...se the current analog reference as torque limit to use it it is necessary to set parameter P5 I_MAX to its maximum vaiue 200 0 ln 4 3 External connections BHL D has some signal terminal boards J1 J2 and a power terminal board N1 The latter exists in two versions indicated hereafter as N1A size 223 Fig 4 2 and N1B size 224 Fig 4 3 Besides terminal boards there are two 9 pin sub D connectors J3 and ...

Страница 36: ...le output 0V 15V for size 224 0V 24V the configuration can be selected on the keyboard with parameter P17 DIG_O2 see paragraph 4 2 J1 12 ØD Zero reference of the board used also as 0V for the auxiliary supply 15V J1 1 and for speed differential input and current analog input J1 13 10V Stabilized supply 10V available externally with maximum load 10mA J1 14 10V Stabilized supply 10V available extern...

Страница 37: ...3 Channel B unipolar output J2 5 Channel TOPØ unipolar output The three unipolar outputs are referred to ØD J2 6 Technical characteristics of the outputs Number of pulses rev programmable resolutions through parameter P36 EN_RES 128 256 512 and 1024 pulses rev Zero notch one pulse rev of width programmable through parameter P37 TOPØ_W Output voltages differential Vout 4V typical Vout 2 5V min Iout...

Страница 38: ...ity see paragraph 3 3 a 6 wire cable twisted and shielded two by two 3x 2x0 25 shielded must be used for connection 4 3 3 Power terminal NI Terminal for size 223 N1A CAUTION lt is important to respect phase sequence for connection to the motor if phases are exchanged the drive may not function Fig 4 2 Terminal for size 224 N1B Fig 4 3 ...

Страница 39: ...cable shield The resolver cable must be of the type approved of by ABB code 16080125 Connections to the plug must comply with drawing DMGCAV067 available on request As regards the connection of the motor thermal probe the standard configuration foresees the short circuit between terminal J4 7 and J4 8 since flag F9 Thermal Probe is set as PTC The motor thermal protection is carried out through I 2...

Страница 40: ...ANIU04 9607 GB 03 97 Page 4 11 4 4 Indications for connections to terminal boards Hereafter you will find some examples of how the convertor should be connected for the start up 4 4 1 Power connection Soft start Power conncetion for SIZE 223 Fig 4 4 ...

Страница 41: ...models 5 10 10 20 14 28 18 36 and compulsory for models 25 50 35 70 50 100 In general the limit circuit must be inserted in all cases where the autotransformer T1 has a nominal power higher than 8kVA this rule is also true in case a single autotransformer supplies more than one convertor The soft start resistors must be short circuited after 150 200 ms from start up they must have a value in the r...

Страница 42: ...A 1 8 3 6 5 0 6 5 9 12 7 18 2 T1 kVA 1 9 3 8 5 3 7 0 9 6 13 3 19 Q1 Q2 16A 16A 16A 25A 25A 40A 63A F1 AM 10A 16A 25A 25A 32A 50A 63A Power cable section 3 T mm 2 1 5 2 5 4 4 6 10 16 4 4 2 Connection for regulation with potentiometer The diagram below exploits the 15V supply available on terminal for enabling and the 10V supply for speed reference using the speed reference input in a non differenti...

Страница 43: ...d regulation The input reference is differential 4 4 4 Connection for torque mode The picture below illustrates a simple application for using the convertor in torque mode To use torque mode see paragraph 4 5 4 The value of the applied signal determines the rms value of the phase current of the motor with a maximum equal to the peak current of the drive The sign indicates the rotation sense of the...

Страница 44: ...inal RE J1 3 and speed reference input on terminal SE J1 4 with this procedure the 7 segment display stands still no more blinking and visualizes 0 At this moment set F1 Auto phasing SET with the keyboard At the end of autophasing the keyboard in correspondence of F1 will display the word DONE for a few seconds and will then go back to CLEAR The resolver phase is automatically memorized in paramet...

Страница 45: ... torque is increased However it is necessary to adjust the dynamic characteristics of the system convertor motor to the mechanical system in which it is used Therefore we advise to adopt such values for KP and KI as to guarantee a good compromise between dynamic performances and noise sensitivity As well as with analog reference the speed command can be set directly with the keyboard At start up t...

Страница 46: ...16 Analog current limit too 4 6 Rules for start up At the moment of installation and start up of the drive You will have to observe the following rules in this order a Make sure that all connections have been carried out according to what prescribed check that all the terminals are tightened in particular the power connections Check that the resolver cable is connected to connector J4 and to the m...

Страница 47: ...the speed digital reference read on the alphanumerical display is zero or it turns slowly if the speed analog reference is enabled and there is an offset in both cases you must supply a positive reference and check that the motor turns counterclockwise To correct the offset of speed analog reference if present there is an automatic procedure see paragraph 4 5 3 2 In these conditions the drive is r...

Страница 48: ...emaining configurations are sensitive to the level The HW limit switch inputs are used to generate an alarm that can be reset only when the limit switch signal becomes H again There are many different possibilities for the management of such an alarm contact Customer Service in case of need For diagnostics two digital configurable outputs and two analog configurable outputs are available on the te...

Страница 49: ...e resolution of the representation with parameters P13 DA1SHF and P15 DA2SHF that determine the number of shifts and therefore the number of divisions by 2 of the numerical value before representing it in an analog way In this way the user can set the use of these signals arbitrarily Since in the majority of cases the most significant numerical values are motor rotation speed and delivered torque ...

Страница 50: ...isplay Moreover you can see the various messages that appear cyclically when one or more alarms are memorized the first line of the alphanumerical display blinks lf various alarms are memorized the message which appears is referred to the alarm with highest priority it increases with the increasing of the number except for I2 t and limit switch alarms Description Codifying Visualization Display 00...

Страница 51: ...ervoltage on the 5 Overvoltage DC BUS Drive disabled Braking Brake module fault 6 circuit fault Drive disabled Fault on the IPM Fault 7 inverter bridge Drive disabled Undervoltage on the 8 Undervoltage DC BUS Drive disabled I2 t motor or Overtemperature protection 9 convertor Drive enabled NOTE All a m alarms are visualized on the alphanumeric keyboard through parameter P28 ALARM After suspension ...

Страница 52: ...de of the cable is specified according to the length the possibility to keep pseudoencoder alive in case of lack of supply by using a separate signal supply The kit related to this function is made up of a personalization inside the convertor and of an external transformer that goes with the convertor This configuration is available please require the suitable code when ordering the convertor Exte...

Страница 53: ...Verkauf Service ABB Automation GmbH Edisonstr 15 D 68623 Lampertheim ABB Telefon Telefax 49 0 6206 503 553 49 0 6206 503 269 ...

Отзывы: