Function name
Signal type
Signal name
Description
EPDMMTR.1.EARALM
Alarm for active reverse energy
exceed limit in set interval
EPDMMTR.1.ERFALM
Alarm for reactive forward
energy exceed limit in set interv
EPDMMTR.1.ERRALM
Alarm for reactive reverse
energy exceed limit in set interv
EPDMMTR.1.EAFDMD_BCR
Last forward active energy
value for set interval (BCR)
EPDMMTR.1.EARDMD_BCR
Last reverse active energy
value for set interval (BCR)
EPDMMTR.1.ERFDMD_BCR
Last forward reactive energy
value for set interval (BCR)
EPDMMTR.1.ERRDMD_BCR
Last reverse reactive energy
value for set interval (BCR)
EPDMMTR.1.EAFACM
Accumulated forward active
energy value in Ws
EPDMMTR.1.EARACM
Accumulated reverse active
energy value in Ws
EPDMMTR.1.ERFACM
Accumulated forward reactive
energy value in VArS
EPDMMTR.1.ERRACM
Accumulated reverse reactive
energy value in VArS
EPDMMTR.1.PAFDMD
Last forward active power
demand value for set interval
EPDMMTR.1.PARDMD
Last reverse active power
demand value for set interval
EPDMMTR.1.PRFDMD
Last forward reactive power
demand value for set interval
EPDMMTR.1.PRRDMD
Last reverse reactive power
demand value for set interval
EPDMMTR.1.MAXPAFDMD
Maximum forward active power
demand value for set interval
EPDMMTR.1.MAXPARDMD
Maximum reverse active power
demand value for set interval
EPDMMTR.1.MAXPRFDMD
Maximum forward reactive
power demand value for set
interval
EPDMMTR.1.MAXPRRDMD
Maximum reverse reactive
power demand value for set
interval
Transformer differential
protection of 2 winding
transformers (TR2PTDF)
Binary inputs
TR2PTDF.1.OPERATE
Operate signal, combined (all
phases, both stages)
TR2PTDF.1.OPR_A
Operate signal phase A
TR2PTDF.1.OPR_B
Operate signal phase B
TR2PTDF.1.OPR_C
Operate signal phase C
TR2PTDF.1.BLKD2H
Status from 2nd harmonic
restraint block, combined
Table continues on next page
1MRS756791 A
Section 2
DNP3 data mappings
630 series
37
Point List Manual