5.4.3
Connecting IED with a test switch
When the IED is used with a test switch, connect the current and voltage
transformers directly to the switch.
5.5
Connecting binary signals
Each signal connector terminal is dimensioned for one 0.5...2.5 mm
2
wire or for
two 0.5...1.0 mm
2
wires.
Table 12:
Binary inputs X304, 4U half 19” and 6U half 19”
Terminal
Description
ACT info
Hardware module
instance
Hardware channel
X304-1
Common - for inputs 1-4
X304-2
Binary input 1 +
COM_101
BI1
X304-3
Binary input 2 +
COM_101
BI2
X304-4
Binary input 3 +
COM_101
BI3
X304-5
Binary input 4 +
COM_101
BI4
X304-6
Common - for inputs 5-8
X304-7
Binary input 5 +
COM_101
BI5
X304-8
Binary input 6 +
COM_101
BI6
X304-9
Binary input 7 +
COM_101
BI7
X304-10
Binary input 8 +
COM_101
BI8
X304-11
Common - for inputs 9-11
X304-12
Binary input 9 +
COM_101
BI9
X304-13
Binary input 10 +
COM_101
BI10
X304-14
Binary input 11 +
COM_101
BI11
X304-15
Common - for inputs 12-14
X304-16
Binary input 12 +
COM_101
BI12
X304-17
Binary input 13 +
COM_101
BI13
X304-18
Binary input 14 +
COM_101
BI14
Table 13:
Binary inputs X319, 4U half 19”
Terminal
Description
ACT info
Hardware module
instance
Hardware channel
X319-1
- for input 1
BIO_3
BI1
X319-2
Binary input 1 +
BIO_3
BI1
X319-3
-
X319-4
Common - for inputs 2-3
Table continues on next page
1MRS755958 C
Section 5
Connecting
630 series
47
Installation Manual
Содержание 630 series
Страница 1: ...Relion Protection and Control 630 series Installation Manual ...
Страница 2: ......
Страница 8: ......
Страница 11: ...Section 10 Glossary 83 Table of contents 630 series 3 Installation Manual ...
Страница 12: ...4 ...
Страница 18: ...10 ...
Страница 44: ...36 ...
Страница 70: ...62 ...
Страница 72: ...64 ...
Страница 90: ...82 ...
Страница 92: ...84 ...
Страница 93: ...85 ...
Страница 94: ......
Страница 95: ......