Section 4
1MAC050144-MB C
Protection functions
286
615 series ANSI
Technical Manual
Figure 135:
Functional module diagram
Directional detector
When “Neg. seq. volt.” selection is made using
Pol signal Sel
, the directional detector
module compares angle of negative sequence current (I
2
) to the negative sequence voltage
(-V
2
). Using the negative sequence voltage angle as the reference the negative sequence
current angle is compared to the
Characteristic angle
. If the angle difference is within the
operating sector selected by
Direction mode
setting then enable signal is sent to the Timer.
The operating sector is defined by the settings
Max forward angle
,
Max reverse angle
,
Min
forward angle
and
Min reverse angle
(see Figure 137). User selectable options for
Directional mode
are “Forward” and “Reverse”.
The value of
Characteristic angle
should be chosen in such way that all the
faults in the operating direction are seen in the operating zone and all the
faults in the opposite direction are seen in the backward zone.
Directional
detector
VN
I2
BLOCK
RELEASE
Blocking
logic
IG
IN
RCA_CTL
Low level
blocking
t
Timer
VG
V2
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......