ABB 2CKT COMBINER 1600389997A Скачать руководство пользователя страница 9

 

QUICK START GUIDE

 

Page 9

 

 

Version 1.0

 

© 2021 ABB. All rights reserved.

 

 

 

Information:  LEDs and Alarms

 

LEDs:  each input and output:  Green OK,  RED Fault.

 

Alarms: Major (MAJ) indicates abnormal output.

 

Minor (MIN) indicates abnormal conditions not immediately affecting output.

 

 

 

 

 

Shelf Output Condition

 

LEDs

 

Circuit Condition (each)

 

Shelf Alarm

 

Out

 

In

 

Normal

 

 

 

Normal

 

None

 

Normal

 

 

 

Never powered

 

None

 

Normal

 

 

 

Blink

 

Not powered, was previously powered

 

MIN

 

Normal

 

 

 

Blink

 

Circuit internal failure, powered

 

MIN

 

Limited 

-

 load power exceeds shelf capability

 

 

 

Circuit in limit mode.

 

MAJ

 

Unpowered

 

 

 

Unpowered.

 

MAJ

 

 

 

 

 

 

 

Specifications and Application 

 

• 

Specifications  and  ordering  information  are  in  the  Power  Express  Class  2  Distribution  Brochure  available  at 

abbpowerconversion.com

 

• 

External Surge Protective Devices (SPD) 

 

• 

Evaluated surge withstand 

-

 1000V, 10/1000 µs pulse. 

 

• 

Primary protection or other surge protection devices are required on each input where the transient over voltage due to 
atmospheric discharge and faults in power distribution systems exceeds these levels.  

 

• 

For example, external SPDs are required when the product is used with outdoor overhead wiring. 

 

• 

Equipment and subassembly ports:

 

 

 are suitable for connection to intra

-

building or unexposed wiring or cabling; 

 

 

 can be connected to shielded intra

-

building cabling grounded at both ends. 

 

• 

Grounding  /  Bonding  Network  –

 

Connect  to  an  Isolated  Ground  Plane  (Isolated  Bonding  Network)  or  an  Integrated 

Ground Plane (Mesh Bonding Network or Common Bonding Network). 

 

• 

Installation Environment 

-

 Install in Network Telecommunication Facilities, OSP, or Restricted Access location. 

 

• 

Equipment must be permanently connected. 

 

• 

DC return may be either Isolated DC return (DC

-

I) or Common DC return (DC

-

C). 

 

• 

Either DC Output polarity (Out+ or OUT

-

) must be externally connected to DC Reference Ground (CO Ground). 

 

Reference Documents 

 

These documents are available at 

abbpowerconversion.com

 

Document       Title 

 

850047711      Power Express Remote circuit combiner 

 

Содержание 2CKT COMBINER 1600389997A

Страница 1: ...QUICK START GUIDE Page 1 Version 1 0 2021 ABB All rights reserved Power Express 2 Circuit and 4 Circuit Combiner Quick Start Guide 8600430826P 1600312215A 4CKT COMBINER 1600389997A 2CKT COMBINER ...

Страница 2: ... Step 3 Connect DC Input 7 Step 4 Connect DC Output 7 Step 5 Connect DC Output to Ground 8 Step 6 Connect Alarm Cable 8 Information LEDs and Alarms 9 Specifications and Applications 9 Change History excludes grammar clarifications 10 Disclaimer 11 List of Figures Figure 1 Mounting Shelf 6 Figure 2 Chassis Ground Connection 6 Figure 3 DC Input Connection 7 Figure 4 DC Output connection 7 Figure 5 A...

Страница 3: ...quipment ratings to assure current does not exceed Continuous Load List 1 60 of protector rating Maximum Load List 2 typically end of discharge 80 of protector rating Field wired Conductors Follow all National Electric Code NEC and local rules and regulations Insulation rating 90 C minimum 105 C minimum if internal to enclosed equipment cabinets Size AC field wired conductors with 75 C ampacity NE...

Страница 4: ... When equipped with ringer modules hazardous voltages will be present on the ringer output connectors Use the following precautions in addition to proper job training and safety procedures Use only properly insulated tools Remove all metallic objects key chains glasses rings watches or other jewelry Follow Lock Out Tag Out LOTO procedures customer specified site specific or general as appropriate ...

Страница 5: ...QUICK START GUIDE Page 5 Version 1 0 2021 ABB All rights reserved Equipment Identification 4 Circuit Combiner ID Label information 2 Circuit Combiner ID Label information ...

Страница 6: ...ormation Tools Required Wire cutters and strippers Philips Screw Driver 0 Cable crimpers Flat Screw Drivers 1 8 and 1 16 Torque wrench 0 40 in lb Sockets 7 16 5 16 Step 2 Connect Chassis Ground 1 Minimum 6 AWG wire is recommended 2 Lug double hole 1 4 on 5 8 centers Lugs not provided 3 Secure lug with screws 10 32 provided 4 Torque to 10 32 screws to 30 in lb 3 4Nm 5 16 socket Some applications ma...

Страница 7: ...lat screw driver torque to 4 5 in oz 0 5 Nm 4 Pull wire to verify connection Caution Ensure cables do not come in contact with sharp or rough surfaces that may damage insulation and cause a short circuit Screw Wire Entry DC Inputs NEC Class 2 Step 4 Connect DC Output There are 2 DC terminal Outputs 1 Use appropriately sized output cable for the load being served 2 Strip the output wire 1 2 3 Inser...

Страница 8: ...ernally connected to DC Reference Ground CO Ground Step 6 Connect Alarm Cable Remove alarm connector from the chassis Connect alarm wires 1 Strip wire 3 16 2 Insert wire fully into wire entry 3 Tighten screw 4 Pull wire to verify Insert alarm connector into the chassis Warning Shock Hazard and Equipment Damage Equipment and subassembly ports 1 are suitable for connection to intra building or unexp...

Страница 9: ...on devices are required on each input where the transient over voltage due to atmospheric discharge and faults in power distribution systems exceeds these levels For example external SPDs are required when the product is used with outdoor overhead wiring Equipment and subassembly ports are suitable for connection to intra building or unexposed wiring or cabling can be connected to shielded intra b...

Страница 10: ...QUICK START GUIDE Page 10 Version 1 0 2021 ABB All rights reserved Version Date Description of the change 1 0 01 04 2022 Initial Release Change History excludes grammar clarifications ...

Страница 11: ... not accept any responsibility whatsoever for potential errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB Copyright 2021 ABB All rights reserved A...

Отзывы: