10.4.2 PROFIBUS PA output
Pos: 23.33 /==== Wechsel ein- auf zweispaltig ==== @ 0\mod_1130421847171_3101.doc @ 3828
Change from one to two columns
Pos: 23.34 /Technische Daten / Datenblatt/Druck/Druckmessumformer/265Dx, 265Vx/PROFIBUS PA-Ausgang @ 5\mod_1164188760546_3101.doc @ 49270
Model
Pressure transmitter conforming to Profile 3.0, Class A and B;
ID number 04C2 HEX
Power supply
The transmitter is operated at 10.2 … 32 VDC (no polarity).
The supply voltage must not exceed 17.5 VDC when used in EEx ia
zones.
Intrinsically safe installation in accordance with FISCO model.
Current consumption
Operating (quiescent):
11.7 mA
Fault current limit value:
Maximum 17.3 mA
Output signal
Physical layer in accordance with IEC 1158-2/EN 61158-2;
transmission using Manchester II modulation at 31.25 kbit/sec.
Output interface
PROFIBUS PA communication according to Profibus DP50170 Part
2/DIN 19245 Part 1-3
Output cycle time
40 ms
Function blocks
265Dx: 2 standard analog input function blocks
265Vx: 1 standard analog input function block
1 transducer block
1 physical block
LCD display (optional)
19-segment alphanumeric display (two lines, six characters) with
additional bar chart display; option of backlighting.
Customized display:
Output value in percent or OUT (analog input)
Diagnostic messages, alarms, measuring range upper limit violations,
and changes to the configuration are also displayed.
Transmitter interference mode
Permanent self-diagnosis; potential errors indicated in diagnostic
parameters and in the status of process values.
Pos: 23.35 /==== Wechsel zwei- auf einspaltig ==== @ 0\mod_1130421955859_3101.doc @ 3829
Change from one to two columns
Pos: 23.36 /==== Leeres Modul mit zwei Absatzmarken, DS, 1-spaltig ==== @ 3\mod_1159257408468_0.doc @ 42813
Pos: 23.37 /Überschriften/1.1.1/1-spaltig/FOUNDATION-Fieldbus-Ausgang @ 5\mod_1165392250328_3101.doc @ 50358
10.4.3 FOUNDATION Fieldbus output
Pos: 23.38 /==== Wechsel ein- auf zweispaltig ==== @ 0\mod_1130421847171_3101.doc @ 3828
Change from one to two columns
Pos: 23.39 /Technische Daten / Datenblatt/Druck/Druckmessumformer/265Dx, 265Vx/FOUNDATION Fieldbus-Ausgang @ 5\mod_1164188958671_3101.doc @ 49291
Power supply
The transmitter is operated at 10.2 … 32 VDC (no polarity).
The supply voltage must not exceed 17.5 VDC when used in EEx ia
zones.
Intrinsically safe installation in accordance with FISCO model.
Current consumption
Operating (quiescent):
11.7 mA
Fault current limit value:
Maximum 17.3 mA
Output signal
Physical layer in accordance with IEC 1158-2/EN 61158-2;
transmission using Manchester II modulation at 31.25 kbit/sec.
Function blocks/execution time
265Dx: 2 standard analog input function blocks/maximum 25 ms
265Vx: 1 standard analog input function block/maximum 25 ms
1 standard PID function block
Additional blocks
1 manufacturer-specific pressure with calibration transducer block
1 enhanced resource block
Number of link objects
10
Number of VCRs
16
Output interface
FOUNDATION Fieldbus digital communication protocol in
accordance with standard H1; complies with specification V. 1.5.
FF registration no.: IT023600
LCD display (optional)
19-segment alphanumeric display (two lines, six characters) with
additional bar chart display; option of backlighting.
Customized display:
Output value in percent or OUT (analog input)
Diagnostic messages, alarms, measuring range upper limit violations,
and changes to the configuration are also displayed.
Transmitter interference mode
Permanent self-diagnosis; potential errors indicated in diagnostic
parameters and in the status of process values.