E LEC TRON I C COM PAC T STA RTE R
| M A N UA L
LED's on the front side
Nominal current [A]
PWR
ERR
Iadj
ON
HF0.6-DOL-24VDC
HF2.4-DOLE-24VDC
HF0.6-DOLE-24VDC
HF9-DOL-24VDC
HF2.4-DOL-24VDC
HF9-DOLE-24VDC
L
R
HF0.6-ROLE-24VDC
HF2.4-ROL-24VDC
HF0.6-ROL-24VDC
HF9-ROLE-24VDC
HF2.4-ROLE-24VDC
HF9-ROL-24VDC
Green
Red
Yellow
0
0
0
0
0.075
0.18
1.5
0
0
0
1
0.110
0.25
2.0
0
0
1
0
0.145
0.41
2.5
0
0
1
1
0.180
0.56
3.0
0
1
0
0
0.215
0.71
3.5
0
1
0
1
0.250
0.87
4.0
0
1
1
0
0.285
1.02
4.5
0
1
1
1
0.320
1.17
5
1
0
0
0
0.355
1.33
5.5
1
0
0
1
0.390
1.48
6.0
1
0
1
0
0.425
1.63
6.5
1
0
1
1
0.460
1.79
7.0
1
1
0
0
0.495
1.94
7.5
1
1
0
1
0.530
2.09
8.0
1
1
1
0
0.565
2.25
8.5
1
1
1
1
0.600
2.40
9
Table 5 Setting the nominal overload current
Example:
Following figure shows a HF-2.4-DOL-24VDC device with a set nominal current of 1.63 A.
—
17 Example for nominal current setting
LEDs on the front side
Nominal current [A]
PWR
ERR
Iadj
ON
HF2.4-DOL-24VDC
HF2.4-DOLE-24VDC
L
R
HF2.4-ROLE-24VDC
HF2.4-ROL-24VDC
1
0
1
0
1.63
Table 6 Illuminated LED at nominal current of 1.63 A
‘PWR’ LED lights in green.
‘ERR’ LED is switched off.
‘Iadj’ / ‘L’ LED lights in yellow.
‘ON’ / ‘R’ LED is switched off.