background image

NOTE

Although a vertical installation of your meter is

best, a horizontal or sloping installation can be

very successful if the meter electrodes are ori-

ented in a horizontal  plane.  If either electrode  is

positioned  at the top, entrapped air may act as an

insulator, resulting in an unreliable measurement.

This tag highlights the installation techniques necessary for depend-
able service from your ABB Magnetic Flowmeter. By observing and
performing these operations, your meter warranty remains valid and
satisfactory performance is assured. Coverage of all recommenda-
tions given in this instruction is provided in detail within the Instruction
Manual which accompanies your meter.

METER GASKETS

Flanges must be

 properly gasketed

Two gaskets are provided in the Installation Kit, as selected for the
particular application.

CONDUIT CONNECTIONS

Conduit seal fittings must be properly installed at the meter primary to
prevent condensate, that may be present in the conduit system, from
entering the customer connection box and degrading meter perform-
ance.

Conduit seals are also required to prevent the process fluid from en-
tering the electrical conduit system. This safety feature considers the
remote possibility of a primary seal failure within the flowmeter, in
which case, this secondary seal will prevent the process from enter-
ing the electrical conduit system in accordance with the National
Electrical Code (NEC) ANSI/NFPA 70, Article 501-5 (f) (3). A cable
seal and mating fittings are supplied with the meter for cables that in-
terconnect with a remotely mounted signal converter. When an inte-
grally mounted signal converter is supplied, cable seals and fittings
are provided only when the accidental submergence option has been
specified.

Proper assembly of the cable
seal and fittings is illustrated
in the adjacent diagram. If the
seal provided contains plugs
in the thru-holes, remove only
those plugs required to ac-
commodate necessary wiring.
The proper use of conduit and
seals provides physical pro-
tection for all external wiring,
makes the meter weatherproof
and provides added assur-
ance against undesireable
stray pick up on signal trans-
mission leads.

FIGURE 3. Typical Conduit Seal

T

IPS &

T

E

CHNI

Q

U

ES

INSTALLATION INSTRUCTIONS

3

Содержание 10D1475

Страница 1: ...INSTALLATION INSTRUCTIONS Magnetic Flowmeter Models 10D1475 1476 1477 PN25001A Trim 1 1 3 i Fini Drill 1 4 To Stock 67 Bindin St...

Страница 2: ...lation of the associated magnetic flowmeter A more detailed de scription of installation procedures will be found in the Instruction Bulletin provided for the particular magnetic flowmeter primary FIG...

Страница 3: ...re supplied by ABB consists of studs nuts gas kets and adapter s Check itemized packing list to be certain that all items listed have been received FIGURE 2 Recommended Piping Diagram OR TIPS TECHNIQU...

Страница 4: ...and degrading meter perform ance Conduit seals are also required to prevent the process fluid from en tering the electrical conduit system This safety feature considers the remote possibility of a pr...

Страница 5: ...s Insert mounting studs through bolt holes Thread nuts on mounting studs finger tight Press down on flange adapter to force spread studs thereby cen tering meter in pipeline Use proper torque and tigh...

Страница 6: ...tween pipe flanges Insert top two mounting studs and sleeves this will center the meter in pipeline install other mounting studs if required Thread nuts on studs Use proper torque and tightening seque...

Страница 7: ...s mandatory for satisfactory operation Perform the applicable grounding procedure Two bonding straps are supplied with the meter for connection to the upstream and down stream pipe flanges Flanges mus...

Страница 8: ...h ground Install grounding ring between pipe flange and meter one up stream and one downstream Refer to FIGURE 7 Two ground straps are supplied with the meter for connection to the upstream and downst...

Страница 9: ...ust be con ductive and not sub ject to chemical reaction with the me tered fluid Grounding rings are available from ABB 2 required Refer to FIGURE 8 FIGURE 8 Outline Dimensions of Accessory Grounding...

Страница 10: ...Road Warminster PA 18974 USA Tel 215 674 6000 FAX 215 674 7183 ABB Instrumentation Ltd Howard Road St Neots Cambs England PE19 3EU Tel 44 0 1480 475 321 FAX 44 0 1480 217 948 ABB Instrumentation S p...

Отзывы: