MODES OF OPERATION 

1. 

Negative Pressure 

- used to help ensure that airborne contaminants do not escape from a contained 

area, by maintaining negative (lower) air pressure within that area compared to adjacent areas. This is 
generally accomplished by placing the unit inside the containment area and exhausting filtered air from 
the unit out of the area. The filtered air must be exhausted outside of the containment area, either 
directly to the outdoors, or into another part of the building. To maintain negative pressure, the air 
exhaust must exceed the air supply by the greater of: 10% or 100 CFM. To achieve this differential, the 
air supply volume to the area may have to be reduced. Negative pressure levels should be continuously 
monitored

 

2. 

Recirculation 

- used to reduce concentrations of airborne contaminants in a room or area by 

continuously cleaning the air and exhausting it back into the same room or area.

 

3. 

Positive Pressure 

- used to help prevent airborne contaminants from entering a containment area, by 

keeping that area under positive pressure compared to adjacent spaces, so any air leakage will be an 
outflow of clean air, and not inflow of contaminated air. This pressure differential can be established by 
placing the unit outside of containment area and using it to push HEPA-filtered air into the area through 
flex duct attached between the outlet collar and a location inside the area. To ensure that the proper 
pressure differential is maintained, the volume of HEPA-filtered air supplied to the area must be the 
greater: of 10% or 100 CFM higher than the volume of air exhausted from it by the HVAC system. 
Positive pressure levels should be monitored continuously.

 

 

Important Note:

 Do not operate the unit unless the pre-filter and HEPA filter are installed and the filter access 

panel is in place. 

 
TO START UNIT 

1. 

Check to make sure that the Speed Control Switch is in the “OFF” position. Plug power cord into a 120 
volt   AC, 60 Hz, 15 amp supply circuit.

 

2. 

Turn Speed Control switch clockwise past the click at the “HIGH” setting to turn power “ON”.

 

3. 

Set Speed Control switch to desired setting.

 

 

Refer to the chart in this instruction manual entitled “AIRFLOW RATINGS” that lists the airflows for the HA700 
and HA700A.

 

 

Note:

 In the event of a power failure while the unit is running or loss of power due to any other cause, this 

unit’s motor will restart when power is restored. 

 
FILTER CHANGE INDICATOR 

The Filter Change Indicator light illuminating (all models), a differential pressure reading of 1.6" WC or greater 
on the Differential Pressure Gauge (HA700A only), and/or the Audible Alarm tone sounding (HA700A only) 
indicate one or more of the following: 

1.  Loaded filter(s). Refer to 

Filter Change Procedure

2.  Restrictions on air intake. Refer to Troubleshooting Guide. 

 

Note: 

The Filter Change Audio Alarm can be deactivated by turning the Audio Alarm Activation Switch "OFF". 

 

FILTER REPLACEMENT 

Note: 

Personnel responsible for changing filters, servicing units or relocating units within the facility are urged 

to wear the proper personal protective equipment and follow safe work practices in accordance with federal, 
state, provincial, and employer regulations. Abatement Technologies cannot recommend the type of PPE 
required as that will need to be determined by safety/risk assessment personnel based on various risk factors, 
including the type of particulates being captured by the air filtration device and the surrounding environment 
where the units are being used, transported, or serviced.

 

 

Note: 

Filters being replaced must be disposed of in accordance with federal, state, provincial, local and facility 

regulations.

 

 

System airflow reduction is generally the result of filter loading, blockage of the unit’s inlet or use of excessive 

Содержание HEPA-AIRE HA700

Страница 1: ...6 HEPA AIRE Portable Air Filtration Unit HA700 and HA700A Instruction Manual Abatement Technologies Inc Abatement Technologies Inc Georgia USA 800 634 9091 Abatement Technologies Limited Ontario Canada 905 871 4720 www abatement com ...

Страница 2: ...ond stage filter 2 Pleated Particulate Pre filter P N H502 Alternative 2 High Capacity Carbon Filter P N VL1002 3 HEPA Filter Retaining Brackets 4 Final Stage 6 Deep 99 97 HEPA Filter P N H161606 99 5 Filter Access Panel 6 Plastic Guides for stacking 7 12 Exhaust Outlet 8 Control Panel 9 Rubber Feet 1 2 3 4 5 7 6 8 9 ...

Страница 3: ...er that are capable of filtering many airborne contaminants An alternative carbon pre filter for capturing low concentrations of odors vapors gases and volatile organic compounds collectively known as OVG is also available Types of contaminants captured by particulate pre filters HEPA filter or carbon filters Dirt Lung damaging particles Low concentrations of OVG Dust Metal fumes Low concentration...

Страница 4: ... filter is reached replace the carbon filter as soon as odor breakthrough is sensed More detailed information on carbon adsorption can be found in an article titled Activated Carbon How Is It Used How Does It Work which can be found on the Abatement Technologies website www abatement com HOW TO DETERMINE THE REQUIRED NUMBER OF AIR FILTRATION DEVICES AFD 1 Calculate the total air volume V in cubic ...

Страница 5: ... an electrical outlet unless the motorized impeller is OFF REQUIREMENTS FOR SAFE OPERATION 1 Never allow unauthorized individuals or children to operate the unit at any time 2 Abatement Technologies urges anyone operating the HA700 and HA700A units to wear the proper personal protective equipment and follow safe work practices in accordance with federal state provincial and employer regulations 3 ...

Страница 6: ...use of intrinsically safe equipment specific engineering controls and personal protective equipment in accordance with Occupational Safety and Health Administration OSHA Environmental Protection Agency EPA Canadian Standards Association CSA and other federal state provincial and local regulations Warning This equipment is not classified as intrinsically safe and should not be used in the following...

Страница 7: ... restriction on intake or loading of the pre filter s and that filter change procedures should be followed Check the Filter Change Indicator when the unit is operating at HIGH speed 6 Filter Change Gauge HA700A only Indicates total system differential pressure in inches of water column WC An increase in differential pressure indicates excessive restriction on intake or loading of the filter s and ...

Страница 8: ...installed and the filter access panel is in place TO START UNIT 1 Check to make sure that the Speed Control Switch is in the OFF position Plug power cord into a 120 volt AC 60 Hz 15 amp supply circuit 2 Turn Speed Control switch clockwise past the click at the HIGH setting to turn power ON 3 Set Speed Control switch to desired setting Refer to the chart in this instruction manual entitled AIRFLOW ...

Страница 9: ...ight is based on the pressure drop across all of the filters it cannot indicate specifically which filter needs to be changed Therefore when the Filter Change Indicator Light illuminates the first stage filter should be changed first to see if the light turns off If the light remains then the second stage filter should be changed If the light remains then the HEPA filter should be changed To Chang...

Страница 10: ...op of unit Stackability The 4 plastic guides on top panel and 4 rubber feet on bottom panel enable up to 3 units to be stacked First stage pre filter 1 deep coarse particulate pre filter P N F621 Second stage pre filter 2 deep pleated particulate pre filter P N H502 Alternative second stage pre filter 2 deep high capacity carbon filter for odors P N VL1002 HEPA filter HEPA mini pleat filter with c...

Страница 11: ...artment at 1 800 634 9091 U S or 1 905 871 4720 Canada for assistance COMPONENT REPLACEMENT AND CARE OF THE UNIT Warning To reduce the risk of fire electrical shock or personal injury always turn the unit OFF and disconnect power cord from supply receptacle before removing the control panel replacing the HEPA filter and before cleaning or servicing the unit The HA700 and HA700A is equipped with an...

Страница 12: ...shall be held for Purchaser s shipping instructions which instructions Purchaser shall furnish promptly upon request ATI s liability shall in no event extend beyond replacement repair or refund of the purchase price and ATI shall not be liable under any circumstances for special contingent or consequential damages nor for loss damages or expenses directly or indirectly arising from the use of the ...

Страница 13: ...12 ...

Страница 14: ...13 ...

Страница 15: ...14 ...

Страница 16: ...15 ...

Отзывы: