![AB Quality GuardPLC 1600 Скачать руководство пользователя страница 14](http://html.mh-extra.com/html/ab-quality/guardplc-1600/guardplc-1600_installation-instructions-manual_450638014.webp)
14
GuardPLC™ 1600 Controllers
Publication 1753-IN001B-EN-P - March 2004
Digital Output Terminals
Terminals accommodate wires up to 1.5 mm
2
(16 AWG). Digital outputs are
connected to the following terminals:
For connection of a load, the reference pole L- of the concerned channel group
must be used (2-pole connection). Although L- at terminals 1 and 6 and at 7 and 12
is connected internally to L- on the power supply input, it is strictly recommended
to use 1 and 6 for outputs 1 through 4 only and 7 and 12 for outputs 5 through 8
only. EMC testing was performed in this manner.
Terminal Number
Designation
Function
Current
1
L-
Reference pole
—
2
1
Digital output 1
0.5 A
3
2
Digital output 2
0.5 A
4
3
Digital output 3
0.5 A
5
4
Digital output 4 (for increased load)
2.0 A
6
L-
Reference pole
—
7
L-
Reference pole
—
8
5
Digital output 5
0.5 A
9
6
Digital output 6
0.5 A
10
7
Digital output 7
0.5 A
11
8
Digital output 8 (for increased load)
2.0 A
12
L-
Reference pole
—
1 2 3 4 5 6
1 2 3 4
1
L-
L-
DO
2
(2A)
3 4
5 6
7 8 9 10 11 12
7 8 9 10
5
L-
L-
DO
6
(2A)
7 8
11 12