background image

Space Temperature Transmitter     

3

Publication 1414-IN012A-EN-P - October 2005

About Space Temperature Transmitter

The unit is designed to convert a 1000 ohm RTD signal and provide a 4 to 20 mA 
analog output with ±0.15°C Class A, ±0.30°C Class B and 0.1% FSO accuracy for the 
board.

Designed for temperature measurement of occupied spaces. Featuring several 
enclosure styles to accommodate various job requirements.

Install Space Temperature Transmitter

Transmitters are mounted directly on a wall or to a wall box. For the most accurate 
results, units should be mounted on an inside wall to a wall box, approximately 3 
to 5 feet from the floor, away from any supply air exhausts and other sources of 
heat or cold. The enclosure cover is held in place with a locking tab located to the 
left of center at the bottom of the enclosure. Remove the setpoint knob before 
removing the cover. Use a set screw (1/16” or 1.5 mm) to lock the cover at the 
bottom of the enclosure after installation.

Wire and Connect Space Temperature Transmitter

Connect the transmitter to the controller using 18 to 22 AWG twisted pair wiring. 
The transmitter requires two wires for DC 4 to 20 mA loop-powered operation. The 
use of shielded cable is optional but recommended for the highest noise immunity. 
Do not route signal wires in the same conduit with power cables as signal 
degradation may occur. The controller Analog Input (AI) must be selected to match 
the transmitter output before power is applied. The AI type must be a current input 
with 250 or 500 ohm impedance. All transmitters have an operating range of 
0 to 70 °C (32 to 158 °F). The transmitter board should not be mounted where 
temperatures exceed these values. See the connection diagram for more details.

Options, if included on your unit, are wired at the Setpoint and Override terminals. 
The Return terminal is used as the common for both of these options. The LCD 
display is powered by the same supply as the transmitter.

Wire to a Programmable Controller

This section indicates typical wiring connections to a programmable controller.

When you use this connection scheme, the nominal setpoint is wired to a 0 to 20 
mA analog input. The setpoint current signal is reverse acting with respect to the 
position of the setpoint slider. The setpoint current varies from 1.2 mA at the 
minimum position to 0.8 mA at the maximum position. An analog input with 14-bit 
resolution provides a resolution of 0.06°F over a range of 60 to 80°F. Analog 

Содержание 1414-CTZ03PBRAA

Страница 1: ...mperature Transmitter Catalog Number s 1414 CTZ03PBRAA 1414 CTD03PBRAA 1414 CTO03PBRAA 1414 CTS03PBRAA 1414 CTT03PBRAA 1414 ITS03PBRAA 1414 ITT03SBRAA 1414 ITZ02GBRAA 1414 ITD02GBRAA 1414 ITO02GBRAA 1414 ITT02SBRAA 1414 ITO03GBRAA 1414 ITS02GBRAA 1414 ITZ03PBRAA 1414 ITD03PBRAA ...

Страница 2: ...stallation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is pro...

Страница 3: ... two wires for DC 4 to 20 mA loop powered operation The use of shielded cable is optional but recommended for the highest noise immunity Do not route signal wires in the same conduit with power cables as signal degradation may occur The controller Analog Input AI must be selected to match the transmitter output before power is applied The AI type must be a current input with 250 or 500 ohm impedan...

Страница 4: ... 20 mA analog input The Common terminal is only wired when the transmitter is used in a 3 wire connection A 2 wire loop powered connection is shown This is the configuration of a 1769 IF4 analog input for the example SETPOINT RETURN OVERRIDE POWER SIGNAL OUT COMMON 24 VDC ANL IN 0 ANL IN 1 ANL IN 0 ANL IN 1 DI 0 DI 1 DI COM Analog Current Input ANL COM 24 VDC Discrete Input Temperature Transmitter...

Страница 5: ...resses the setpoint in degrees F withouit further converstion Specifications Setpoint Input Data Range Slider Position Temperature Setpoint Engineering Units Minimum 60 F 1200 1 2 mA Maximum 80 F 800 0 8 mA Space Temperature Transmitter Specifications Specification Value Transmitter Accuracy 0 1 FSO Temperature Sensor Type 1000 ohm platinum RTD 0 15 C 0 3 C Output Signal 4 20 mA current loop CPT C...

Страница 6: ... sensor Loop Current Maximum 22 5 mA nominal occurs with open sensor Maximum Loop Load 600 ohms at 24 Vac dc with no LCD 325 ohms with LCD Protection Circuitry Reverse voltage protected and output limited Display Accuracy 0 2ºF over full range with respect to the output signal Display Units ºF Factory set Display Range 32 0 95 F Display Resolution 0 1ºF for display of 00 0 to 99 9 Slide pot 20 30K...

Страница 7: ...Space Temperature Transmitter 7 Publication 1414 IN012A EN P October 2005 ...

Страница 8: ...005 PN 40055 242 01 1 Supersedes Publication XXXX X X X Month Year Copyright 2005 Rockwell Automation Inc All rights reserved Printed in the U S A All other trademarks are the property of their respective holders and are hereby acknowledged ...

Отзывы: