General manual. Rechargeable lead

-

acid batteries ZEUS.

 

4

 

AAT SYSTEMY BEZPIECZEŃSTWA sp. z o.o.

 

All rights reserved.

 

 

 

Correction of the charging voltage depending on the ambient temperature

 

As  the  temperature  rises,  the  electrochemical  activity  of  the  battery  increases.  When  the  temperature  drops,  the 
electrochemical  activity  of  the  battery  also  drops.  In  case  of  an  increase  of  temperature,  the  charging  voltage  should  be 
reduced to prevent overcharging of the battery. If the temperature drops, the charging voltage must be increased. In order 
to  maintain  the  optimal  battery  life  in  the  event  of  large  fluctuations  in  operating  temperature,  a  power  supply  with  a 
charging  voltage  temperature  compensation  system  should  be  used,  which  reduces  the  charging  voltage  with  increasing 
temperature. The temperature compensation coefficient for ZEUS batteries is 

-

20 [mV / °C / cell] in buffer operation and 30 

[mV / °C / cell] in cyclic operation at 25°C. The characteristics presented below show the relationship between temperature 
and charging voltage: 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Operating temperature

 

The  location  of  battery  is  very  important  to  the  life  and  capacity  of  the  battery.  The  nominal  operating  temperature  of 
maintenance

-

free  batteries  is  20°C.  Operation  at  temperatures  above  20°C  shortens  the  battery  life.  Any  increase  in 

temperature 8 to 10°C above the nominal value reduces the battery life by half. For example, the service life of a battery 
operated at 30°C will be reduced by half.

 

 

General storage conditions

 

The battery should be stored in a dry, cool and clean place with low humidity. The room temperature should be between 15 
and 40°C.

 

After long

-

term storage, the battery capacity may be less than recommended. In order to obtain the capacity recommended 

by the manufacturer, the battery should be subjected to several charge / discharge cycles (usually two cycles).

 

In order to ensure proper operation after storage, it is recommended to periodically charge the batteries at the following 
intervals:

 

 
 
 
 
 
 
 
 

Installation

 

Install the battery in a clean and dry room. Under normal operating conditions, the battery does not emit any gases, so it 
can work indoors with other electrical devices.

 

 

Note!

 

All  data  may  be  changed  without  notice,  AAT  SYSTEMY  BEZPIECZEŃSTWA  sp.  z  o.o.  reserves  the  right  to  explain  and 
updated the information

 

Ambient temperature

 

 Recommended interval

 

below 20°C

 

12 months

 

from 20 to 30°C

 

6  months

 

from 30 to 40°C

 

3 months

 

Relationship Between Charging 

Voltage And Temperature  

 

Temperature (°C)

 

Ch

ar

ge

 Vo

ltage 

(V)

 

Отзывы: