KDH

-

ZAS12/6/17 

-

 Installation manual

 

 

 

 

 

 

 

AAT SYSTEMY BEZPIECZEŃSTWA Sp. z o.o.

 

           All rights reserved.

 

1

 

Installation manual

 

Power supply for access control controllers

 

KDH

-

ZAS12/6/17

 

 

Version 3.0 ENG   19.09.2022

Содержание KaDe KDH-ZAS12/6/17

Страница 1: ...KDH ZAS12 6 17 Installation manual AAT SYSTEMY BEZPIECZEŃSTWA Sp z o o All rights reserved 1 Installation manual Power supply for access control controllers KDH ZAS12 6 17 Version 3 0 ENG 19 09 2022 ...

Страница 2: ...al Before putting the device into operation check the quality of all connections made The device may disrupt the operation of sensitive radio and television equipment located in the vicinity The device may only be serviced by the manufacturer s service or specialized units authorized by the manufactu rer Handling packages used products and batteries The product packaging is made of materials that ...

Страница 3: ... battery bank The connection to the 18Ah battery which is equipped with screw terminals is made through a transition element a male 6 3mm connector with a Ø6mm hole The current outputs of the PSU and its relay signaling outputs are connected by connectors equipped with screw terminals The connection can be made both when the connector caps are already mounted in the power supply and after their re...

Страница 4: ... A Floating operation voltage 13 5 13 6 13 7 V Low battery voltage indication 11 2 11 4 11 6 V Automatic disconnection of the discharged battery 10 5 10 8 11 0 V Power consumption from the battery for own needs Battery connected 65 mA Battery connection method permanently connected cables 1 5mm2 250mm ended connectors 6 3mm 2 szt Relay signaling outputs Characteristics of outputs NO Relays Max Cap...

Страница 5: ...anual AAT SYSTEMY BEZPIECZEŃSTWA Sp z o o All rights reserved 5 1 3 Dimensions The power supply is prepared for wall mounting The figures below show the closed power supply with its di mensions and the spacing of the mounting holes ...

Страница 6: ...LED signaling which repeats the signaling on the printed circuit board Nr Description Symbol 1 230V power connector terminals L N PE 2 Output 1 terminals OUT 1 3 LED indicating voltage presence at the OUT1 4 Output 2 terminals OUT 2 5 LED indicating voltage presence at the OUT2 6 Low battery voltage signaling relay output LOW BAT 7 Mains power loss signaling relay output MAIN FLT 8 Battery fuse 9 ...

Страница 7: ...e cannot be replaced be cause its blown is a sign of serious damage The power supply is designed to work with a 12V battery the so called maintenance free which should be placed in the cabinet after mechanical and electrical assembly is completed Pay particular attention to the polarity of the connection betwe en the PSU module and the battery pack If the connection is incorrect the battery circui...

Страница 8: ...onowy dla m st Warszawy w Warszawie XIII Wydział Gospodarczy Krajowego Rejestru Sądowego pod numerem KRS 0000838329 kapitał zakładowy wpłacony w całości w wysokości 5 000 zł NIP 9512500868 REGON 385953687 Wpisana do rejestru przedsiębiorców prowadzonego przez Sąd Rejonowy dla m st Warszawy w Warszawie XIII Wydział Gospodarczy Krajowego Rejestru Sądowego pod numerem KRS 0000838329 kapitał zakładowy...