AAP TRX Mains Скачать руководство пользователя страница 11

1– Set On Time 1. 

  P 172 E 1 E (enter start time is 24hr format 0000-2359) 

 

 

2- Set Off Time 1. note Off time must be after On time. 

  P 173 E 1 E (enter finish time is 24hr format 0000-2359) 

 

3- Set Timer 1 Days of Week. 

  P 171 E 1 E (put in day active days 1-7, see table) 

4- Assign Timer 1 to an Output. 

  P 44 E (enter output number )                  E 1 

5– Changing Reset Timer of Output.  

  P 40 E                    E 0 

 

Need another On and Off sequence? Follow the steps below. 

6– Set On Time 2. 

  P 172 E 2 E (enter start time is 24hr format 0000-2359) 

 

 

7- Set Off Time 2. note Off time must be after On time. 

  P 173 E 2 E (enter finish time is 24hr format 0000-2359) 

 

8- Set Timer 2 Days of Week. 

  P 171 E 2 E (put in day active days 1-7, see table) 

9- Assign Timer 2 to an Output. 

  P 44 E (enter output number)                 E 2 E 

No.  Day 

1 =  Sunday 
2 =  Monday 
3 =  Tuesday 
4 =  Wednesday 
5 =   Thursday 
6 =   Friday 
7 =   Saturday 

Page 11 

Automatic On/Off timer (Recommended for Heated Towel Rail)

 

There are 8 different On/Off timers that can be set in the Elite-S series control panel. 

Before starting the Programming steps below make sure the TRX Mains has been paired to the TRX 

Transceiver (see page 6) and an Output number has been assigned (see page 7). 

 

*Programming below is done from the Control Panel Keypad in Installer Mode. 

Smart Features 

 

Automatic Turn Lights Off when System Arms

 

Each Output (TRX MAINS) can be Selected to turn Off when the Alarm System is Armed. 

 

*Programming below is done from the Control Panel Keypad in Installer Mode. 

 

P 54 E 1 E 

(each TRX Mains number can be turned on here) 

 

Note. Don’t turn on 1 or 2 this will trigger the sirens 

Adjusting Lights On Exit Timer

 

Once you have turned On the option above, you can choose to extend the Off delay time up to 25 sec-

onds. This will give you an illuminated exit from the property before turning the lights Off. 

Each Output (TRX MAINS) can be adjusted individually. 

 

*Programming below is done from the Control Panel Keypad in Installer Mode. 

 

P 39 E  

time in 10ths/second 1-255 E (250 = 25seconds) 

 

Note. Repeat the process for each TRX MAINS you wish to have this feature 

Fallback Feature 

 

If communication is lost to the TRX Transceiver, the TRX Mains will automatically Fallback and operating 

directly from it’s Trigger Input.  

 

Содержание TRX Mains

Страница 1: ...40VAC 50Hz Current Draw 5mA Max Switching Current 8A Resistive Load 6A Inductive Load Frequency 917 1 921 3 MHz Connection 1 Neutral In 2 Phase Trigger Input 3 Phase In 4 Switched Phase Output 8Amp Max Manufactured by Arrowhead Alarm Products ltd 344b Rosedale rd Albany Auckland New Zealand Ph 09 414 0085 www aap co nz LOAD 8A MAX Page 1 ...

Страница 2: ...TRX MAINS In Wall Installation Page 2 FLUSH BOX ...

Страница 3: ...onal Trigger Input Plastic Enclosure Installation Use Electrically Approved Plastic Enclosure Only Do Not Mount TRX MAINS in a Metal Enclosure Suitable Enclosures TB AG 1010 100 x 100mm TB AG 1115 110 x 150mm Page 3 ...

Страница 4: ...hase In Neutral In TRX MAINS Phase Out 230VAC 230VAC Page 4 Mounted inside plastic enclose TB AG 1115 110 x 150mm Warning The TRX Mains relay is not suitable for mounting in accessible locations It must be installed within an enclosure providing suitable insulation as shown above Optional Override Input ...

Страница 5: ...Page 5 Phase Out Neutral Out Phase In Neutral In Switch 1 TRX MAINS LOAD 8A MAX Switch 2 2 Way Light Switching Example Existing Wired Solution ...

Страница 6: ...0 seconds or press the red button to make it stop Option 2 Pairing to Transceiver using IR Remote 10 1 Safely apply power to the TRX MAINS 2 Point the IR remote at the bottom of the TRX MAINS see diagram c and press P then E The TRX MAINS will start beeping as it searches for a device to pair with 3 Now put the TRX TRANSCEIVER connected to the ELITE S into pairing mode by pressing and hold ing the...

Страница 7: ...ime is only 2 seconds P 40 E 3 E 0 E lights now will not automatically turn off 5 1 Learn State 1 ON to the first User slot P 18 E 92 E E when beeping starts flick the switch connected to the TRX Mains On 2 Learn State 2 OFF to the second User slot if you have a momentary switch skip this step P 18 E 93 E E when beeping starts flick the switch connected to the TRX Mains Off 3 Adjusting Output Rese...

Страница 8: ...to be changed P 4 E E turn Off all options E 4 Output Mapping for State 1 P 12 E E E 5 Output On Command for State 1 P 13 E E E 6 Output Off Command for State 1 P 14 E E E 7 Output Permission P 34 E E turn On option 6 E 8 Output Reset Time P 40 E E turn On option 6 E 9 Set the User Assignment P 4 E E turn Off all options E 10 Output Mapping for State 2 P 12 E E E 11 Output On Command for State 2 P...

Страница 9: ...o Group Mode you must use the IR Remote 10 1 Safely apply power to the TRX MAINS 2 Point the IR remote at the bottom of the TRX MAINS see diagram c and press P 0 then E The TRX MAINS will give a triple beep if accepted Programming Options Programming below is done from the Control Panel Keypad in Installer Mode Lights Off when System is Armed P 47 E 1 E turn 8 On E Lights On when System is Disarme...

Страница 10: ...e Input Earth In To Heated Towel Rail 8A Max Mounted inside plastic enclose TB AG 1010 100 x 100mm Warning The TRX Mains relay is not suitable for mounting in accessible locations It must be installed within an enclosure providing suitable insulation as shown above Page 10 ...

Страница 11: ...e starting the Programming steps below make sure the TRX Mains has been paired to the TRX Transceiver see page 6 and an Output number has been assigned see page 7 Programming below is done from the Control Panel Keypad in Installer Mode Smart Features Automatic Turn Lights Off when System Arms Each Output TRX MAINS can be Selected to turn Off when the Alarm System is Armed Programming below is don...

Страница 12: ...414 0085 Fax 09 414 0088 www aap co nz v1 01 Page 12 Warning This unit contains no user serviceable parts it must be returned to the manufacture if it fails to operate or the cable is damaged Install only as per manufactures instructions and or in recommended enclosure ...

Отзывы: