60
Unit Configuration
Water-Cooled Condenser
Air-Cooled Condenser
No Water Leaks
Condenser Safety Check
Water Flow ________ gpm
Water Inlet Temperature ________°F
Water Outlet Temperature ________°F
Water/Glycol System
1.
Has the entire system been flushed and pressure checked?
Yes No
2.
Has the entire system been filled with fluid?
Yes No
3.
Has air been bled from the heat exchangers and piping?
Yes No
4.
Is the glycol the proper type and concentration (N/A if water)?
Yes No
5.
Is there a minimum load of 50% of the design load?
Yes No
6.
Has the water piping been insulated?
Yes No
7.
What is the freeze point of the glycol (N/A if water)? ______________________________
Air-Cooled Condenser Fans
Alignment
Check Rotation
Nameplate Amps________
Number
hp
L1
L2
L3
1
2
3
4
5
6