
RSMV-HP Technical Guide
APPENDIX: CONDENSER OPTIONS
25
Single Condenser Per Two Modules
Single Condenser Per 2 Modules
In Single Condenser Per 2 Modules wiring confi guration, if using 2
modules, the Condenser Signal is wired to AO2 on the 1st module
but not the 2nd module and the Condenser Relay RLY3 is enabled
on the 1st module but not the 2nd module.
RSMV & RSMV-HP Condenser Options
Con
fi
guration Screen
RSM#1-4 CONFIGURATION
Condenser Options
1 Cond per 2 RSMVs
USE < or > TO CHANGE
Select the “1 Condenser per 2 RSMVs” option on the above Hand
Held Service Tool Screen.
Figure 7: Prism 2 Condenser Confi guration
If using 4 modules, the Condenser Signal is wired to AO2 on the 1st
and 3rd modules but not the 2nd and 4th modules and the Condenser
Relay RLY3 is enabled on the 1st and 3rd modules but not the 2nd
and 4th modules.
Refer to the fi gures below for Prism 2 confi guration and Modular
Service Tool Screen selection.
Содержание RSMV-HP
Страница 1: ...RSMV HP Technical Guide ...
Страница 29: ...RSMV HP Technical Guide NOTES 29 ...
Страница 30: ...NOTES RSMV HP Technical Guide 30 ...
Страница 31: ...RSMV HP Technical Guide NOTES 31 ...