Full Digital Module

Technical Guide

14

Connect To

E-BUS

Distribution

Module

Line Voltage

24 VAC

GND

Line Voltage

All Comm Loop Wiring Is

Straight Thru

24VAC

GND

Local Loop

RS-485

9600 Baud

See Individual Component

Wiring Diagrams For

Detailed Wiring Of Analog

Inputs And Outputs

For Stand Alone Applications,
Connect To System Manager.

For Network Applications

Connect To Next Controller

And/Or MiniLink PD On Local Loop.

G - Fan ON/OFF  Only

R - 24VAC

Relay Output Contacts
R2 Through R5 May Be User-Configured
For The Following:

1 - Heating Stages
2 - See Note 1 Below
3 - Warm-up Mode Command (VAV Boxes)
4 - Reversing Valve (Air To Air Heat Pumps)
5 - Reheat Control (Dehumidification)
6 - Exhaust Fan Interlock
7 - Preheater For Low Ambient Protection
8 - Alarm
9 - Override
10 - Occupied
11 - OA Damper
12 - Heat Wheel
13 - Emergency Heat
Note: 1.) When Using the HP2C Module,
All Compressors Will Be Wired From the
Protection Module, Not the VCM-X
Controller.
2.) A Total Of 20 Relays Are Available By
Adding Relay Expansion Modules. All
Expansion Module Relay Outputs Are User-
Configurable As Listed Above.

Connect FRP Tubing To High Pressure
Port  (Bottom Tube) and Route To Static
Pressure Pickup Probe Located In Unit
Discharge. Leave Port Marked “Lo” Open
To Atmosphere

OE271

Static Pressure

Transducer

Splice If Required

Connect To E-BUS Distribution Module
or Expansion Module(s) (When Used)

Connect To Digital Room Sensor And/Or
Digital CO Sensor

2

Warning:
24 VAC Must Be Connected So That All Ground
Wires Remain Common. Failure To Do So Will
Result In Damage To The Controllers.

T to T, R to R & SHLD to SHLD

Size Transformer For
Correct Total Load.
VCM-X Modular Controller
= 8 VA

OE332-23-VCMX-MOD-A

VCM-X Modular Controller

Note:

All Relay Outputs Are Normally Open And Rated
For 24 VAC Power Only.
1 Amp Maximum Load.

AI1

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

Jumpers

Figure 6:  VCM-X Modular Controller Connection to Full Digital Module

Appendix

VCM-X Modular Controller to Full 

Digital Module Wiring

When using the VCM-X Modular Controller, the E-BUS Distribution 
Module is required ot connect to the Full Digital Module. The Full Digital 
Module connects to the E-BUS Distribution Module using a modular 
HSSC cable. The Full Digital Module requires a 24 VAC power con-
nection with an appropriate VA rating.

The E-BUS Distribution Module connects to the VCM-X Modular 
Controller, VCM-X Expansion Module, or 12 Relay Expansion Module 
using the I

2

C port. See 

Figure 6

 below for wiring. 

Any E-BUS module can be connected to each of the four E-BUS

 

Dis-

tribution Module’s output ports or can be daisy-chained together using 
HSSC cables. 

If using a spliced terminal connection for longer runs, one module can be 
connected to the E-BUS Distribution Module and any additional modules 
would be daisy-chained to the 

fi

 rst module. For more information, refer 

to the 

E-BUS Distribution Module Technical Guide.

Содержание R90800

Страница 1: ...Full Digital Module Technical Guide Factory Packaged Controls Tulsa...

Страница 2: ...0 PH 816 505 1100 FAX 816 505 1101 E mail mail wattmaster com Visit our web site at www orioncontrols com WattMaster Form AA FDM TGD 01G Copyright July 2016 WattMaster Controls Inc AAON Manual Part Nu...

Страница 3: ...e Module OE370 23 HP1C is also installed Module Overview Figure 1 Full Digital Module The Full Digital Module is connected to the VCM X Modular Control ler using the E BUS Distribution Module OE365 23...

Страница 4: ...standard I2 C modular cable to connect with the VCM X Modular Controller VCM X Expansion Module or 12 Relay Expansion Module The Full Digital Module can also be directly connected to the VCM X Modula...

Страница 5: ...UT COM COM COM EXC EXC EXC P4 P4 P4 BK BK BK RD RD RD WH WH WH P2 P2 P2 P1 P1 P1 P3 P3 P3 P5 P5 P5 C1 C1 C1 C2 C2 C2 P6 P6 P6 SHLD OUT COM EXC P4 BK RD WH P2 P1 P3 P5 AO1 SIG 1 SIG 2 SIG 3 SIG 4 AO2 G...

Страница 6: ...r lengths and 100 and 150 foot lengths Figure 4 VCM X Modular E BUS Controller to Full Digital Module Wiring Diagram Connect To Other WattMaster Approved E BUS Expansion Module s HSSC Cable HSSC Cable...

Страница 7: ...mon Failure To Do So Will Result In Damage To The Controllers T to T R to R SHLD to SHLD Size Transformer For Correct Total Load VCM X Modular Controller 8 OE332 23E VCMX MOD A VCM X Modular E BUS Con...

Страница 8: ...e to observe polarity could result in damage to the boards Table 1 Unit Configurations Chart UNIT CONFIGURATIONS PERMUTATION SYSTEM A SYSTEM B HARDWARE VCM X WSHP CONFIGURATION Comp A1 Comp A2 Comp B1...

Страница 9: ...ital Stage 2 outputs will go to 50 and begin to modulate together If both systems are energized and they go below 30 and the SupplyAir is below the Supply Air Setpoint by the Cooling Stage Window valu...

Страница 10: ...diagnostic blink code LED It will light up and blink out diagnostic codes See Table 2 for Diagnostic Blink Code descriptions The blink code descriptions are also located on the mod ule s front cover N...

Страница 11: ...ctive R3 This LED will light up when Compressor B1 is enabled and will stay lit as long as Compressor B1 is active R4 This LED will light up when Compressor B2 is enabled and will stay lit as long as...

Страница 12: ...If the COMM LED does not blink then communications have not been established Check the connection between the VCM X Modular Con troller the VCM X Modular E BUS Controller the E BUS Distribution Modul...

Страница 13: ...e and Voltage Chart for R410A Refrigerant testing Table 4 The chart shows a temperature range from 20 F to 80 F For troubleshooting pur poses the DC Voltage readings are also listed with their corresp...

Страница 14: ...Digital Room Sensor And Or Digital CO Sensor 2 Warning 24 VAC Must Be Connected So That All Ground Wires Remain Common Failure To Do So Will Result In Damage To The Controllers T to T R to R SHLD to...

Страница 15: ...COMM GND VDC 485 DRV 24VAC GND PWR YS102308 REV 1 I2C TO COMM DIST BOARD OUTPUT Modular Cable Connect To VCM X Modular Controller HSSC Cable Connect To E BUS Distribution Module Connect To Other Watt...

Страница 16: ...2425 So Yukon Ave Tulsa OK 74107 2728 Ph 918 583 2266 Fax 918 583 6094 AAON Manual Part No R84500 WattMaster Manual Form No AA FDM TGD 01G www aaon com...

Отзывы: