background image

ASM01883 

PT-Link II LON-3

®

Installation Sheet

PT-Link II LON-3

®

 Overview

The PT-Link II LON-3

®

, provides bi-directional communication between

 

ONE* of the following types of Orion controllers—VCCX2, VCC-X, 

VCB-X, VCM-X, SA, VCM, MUA II, or VAV/CAV:

 

VCCX2 Controller (SS1088)
VCC-X Controller (SS1079)

VCB-X Controller (SS1051)
VCM-X Controller (SS1026, SS1030, SS1032, SS1033,  

SS1034, Y200920)
SA Controller (Y200921)
VCM Controller (SS1016, Y200409, Y200616, Y200822)
VAV/CAV Controller (SS1003, Y200301) and  

MUA II Controller (SS1004, Y200405)

To determine what controller you have, you must look at the software 

label located on the controller. 

NOTE:

 The label is located on the 

EPROM on older devices. If the controller label does not match any of 

the SS or Y numbers listed above, your controller will not work with 

the PT-Link II LON

®

*NOTE:

  The PT-Link II LON

®

 device can be used to connect to   

  only one Orion controller. If more than one Orion control- 

  ler is present in a system, each one will require a PT-Link  

 II LON

®

 device for integration with a LON

®

 protocol  

 network.

Data Sharing and Scheduling

• 

Provides values from points on the Orion side of the  

 

 

gateway to LON

®

 devices as if the values were 

 

originating from LON

®

 objects.

• 

Allows LON

®

 devices to modify point values on the  

 

 

Orion controller side of the PT-Link II LON

®

 by using  

 

 standard 

LON

®

 write services.

Includes:  PT-Link II LON-3

®

 Controller, 10 Foot CAT5e Crossover Cable,   

(3) Self-drilling 8 x 1” Hex Head Screws, PT-Link II Flash Drive

Technical Data

LON

®

 Loop

TP/FT-10 (78 Kps)

Orion Controller Loop

RS-485, 9600 Baud Rate

Network Protocol 

LONWorks

®

Orion Controls Protocol  

Communications

HSI Open Protocol Token Passing

Power Input Voltage

18-30 VAC

Power Consumption

10 VA Maximum

Operating Temp

-30°F to 150°F

Operating Humidity

0-95% RH Non-Condensing

Weight

4.7 oz.

Table 1:  PT-Link II LON-3

®

 Technical Data

System Requirements

• 

Computer running Microsoft

®

 Windows

®

 10

   

 

operating system.

• 

Ethernet Crossover Cable (supplied).

•  PT-Link LON

®

 and RUINET software— 

 

included on flash drive and also downloadable 

 

 

from www.aaon.com/controlstechsupport

•  Prism 2 software—downloadable from  

 www.aaon.com/prism

Hardware Specifications

The PT-Link II LON-3 Technical Guide 

is located on the included flash drive 

and can also be downloaded from www.

aaon.com/PTLink

Отзывы: