General Information
The AAON Mini Controller has been
designed for simple single zone system
control.
Codes and Ordinances
HVAC
system
should
be
sized
in
accordance with the American Society of
Heating, Refrigeration and Air Conditioning
Engineers Handbook.
Installation of equipment must conform to
the ICC standards of the International
Mechanical Code, the International Building
Code, Installation of Air Conditioning and
Ventilating Systems Standard, NFPA 90A,
and local building, plumbing and waste
water codes. All appliances must be
electrically grounded in accordance with
local codes, or in the absence of local codes,
the
current
National
Electric
Code,
ANSI/NFPA 70 or the current Canadian
Electrical Code CSA C22.1.
Receiving Unit
When received, the controller should be
checked for damage that might have
occurred in transit. Controller should also be
checked to ensure the correct model has
been received to match the job requirements.
AAON Mini Controller
R80570 - Space Temperature Control
R80580 - Space Temperature and Humidity
Control
Specifications
Supply Voltage:
24 VAC (+15%/-10%), Class-2
Supply Power:
13 VA
Connections:
Wire clamp type terminal blocks; 14-22
AWG, copper; 4 pin EIA-485
Outputs:
Analog outputs produce 0-10 VDC, 20 mA
maximum.
Binary outputs (N.O. SPST, Form A) carry 1
A maximum per relay or a total of 1.5 A per
bank of 3 relays (relays 1-3, 4-6) @ 24
VAC/VDC
Inputs:
10k Type 3 Thermistor
Display:
64 x 128 pixel dot matrix LCD
Case Material:
White flame retardant plastic
Dimensions:
5.551 x 4.192 x 1.125 inches (H x W x D)
141 x 106 x 28.6 mm
Weight:
0.48 lbs, 218 g
Approvals:
UL 916 Energy Management Equipment
FCC Class B, Part 15, Subpart B
Temperature/Humidity Sensors:
10k Type 2 Thermistor (Temperature only
model)
CMOS (Temperature and Humidity model)
Temperature Readings
Accuracy:
+/-0.9°F (+/-0.5°C) from 40-104°F
Resolution:
+/- 0.1°F (+/-0.2°C)
Operating Range:
36-120°F (2.2-48.8°C)
Response Time:
5-30 seconds
Improper
installation,
adjustment,
alteration, service or maintenance
can
cause
property
damage,
personal injury or loss of life.
Installation and service must be
performed by a trained, qualified
installer. A copy of this manual
should be kept with the unit.