MHGRVX-A2 Module Technical Guide
WIRING
MHGRVX-A2 Stand-Alone Wiring
Stand-Alone Wiring
In Stand-Alone Mode, the MHGRVX-A2 connects to the E-BUS
port of the Reheat Expansion Module with an E-BUS cable. See
Figure 3,
this page
.
See the SAT Wiring Conditions and SAT OPTIONS Jumper Settings
in
Tables 8 and 9, page 26
.
GND
RED
GRN
WHT
BLK
Condenser Valse #1
HGR Valve #1
RED
GRN
WHT
BLK
Compressor
Flush Active Signal
or Compressor 2
Two Position HGR Valve
or Reversing Valve
C1
C2
COMM
E-BUS cable connects to the
Reheat Expansion Module
Line
Voltage
40 VA
transformer
minimum
18-30 VAC
Fan
+
-
See SAT OPTIONS table for
Jumper Settings.
Only one Supply Air Temperature
Sensor can be used per application.
0-10 VDC
External Reset
Signal
H1 (Dehumidification)
Heating Override
Cooling Override
Mount in
Supply Air
Duct
Supply Air
Temperature
Sensor
D8
R2 J3
MODGASx
MODGAS
NORMAL
R1
SAT OPTIONS
SAT
GND
COOL OVRD
HEAT OVRD
REHEAT EN
RESET IN
AUX IN
GND
TB2
LC
FAN
COMP
VALVE
AUX
COMMON
TB1
STATUS
ALARM
COMM
POWER
CONDENSOR DRIVE
BLACK
WHITE
RED
GREEN
OPENING
TB3
REHEAT DRIVE
BLACK
WHITE
GREEN
RED
OPENING
TB4
C23
.01uF
ALARM
UP
DOWN
ENTER
MENU
FAN
COMPRESSOR
REHEAT VALVE
AUX
COMMON
OUTPUTS
RELAY
CONDENSER
DRIVE TERMINALS
BLACK
WHITE
RED
GREEN
GND
RHT EN (BI)
AUX INPUT (AI)
RESET SIG (AI)
HEA
T OVR (BI)
COOL
OVR (BI)
INPUT TERMINALS (
TYPE)
GND
SA
T (AI)
@ 24 VAC
CONTACT
RATING IS
1 AMP MAX
MHGRVX-A2
AAON P/N: ASM06926
www.aaon.com
LABEL P/N:
G112600
E-BUS
CONNECT
CONNECT
E-BUS
+24V
AC
GND
REHEAT VALVE
DRIVE TERMINALS
BLACK
WHITE
GREEN
RED
Figure 3: MHGRVX-A2 Stand-Alone Wiring