48
circle, in the form of washers, and/or longer
bolts, or an additional balancing nut.
Number the blades and blade sockets, so that
they are replaced into their original position.
Figure 27 - Fan with the HUB on the top and
RET on the bottom.
2.
Determine the direction of rotation
Right, R, is clockwise when facing the
discharge side of the fan and Left, L, is
counterclockwise when facing the discharge
side of the fan.
3.
Determine the bushing mount location
The bushing mount is the center section of the
hub through which the fan is mounted to the
shaft, and typically contains either setscrews
or a center-tapered hole where the bushing
inserts.
Location A is with the bushing mount on air
inlet side of the fan.
Location B is with the bushing mount on air
discharge side of the fan.
Figure 28 - Bushing Mount Location
4.
Determine the pin location groove
Disassemble fan on a flat surface and note in
which groove the pin is located.
Figure 29 - RET with Pin in Groove 4
5.
Determine whether the pin is in the HUB
or RET
Figure 30 - Fan HUB and RET Castings
Bushing
Mount
A
B
Bushing
Mount
Bushing
Bushing
1 2 3 4
Содержание LZ Series
Страница 2: ......
Страница 27: ...27 Figure 6 Concrete Pad Mounting with Dimensions Figure 7 LZ Base ...
Страница 36: ...36 Figure 17 Typical Flue Vent Piping ...
Страница 40: ...40 Figure 24 Typical Vertical Vent Piping Figure 25 Vertical Termination of Air Intake and Vent Piping ...
Страница 83: ...83 ...
Страница 84: ...84 ...
Страница 95: ...95 Flo Trex Cross Section ...