26
Electrical
Verify the unit nameplate agrees with power supply. Connect power and control field wiring as
shown on the unit specific wiring diagram provided laminated and attached to the door in the
controls compartment.
Table 4 - Nameplate Voltage Markings & Tolerances
Hz
Nameplate
Voltage
Nominal
System
Voltage
Operating Voltage Range
1
Acceptable Performance
Range
2
Min
Max
Min
Max
60
115
120
104
127
108
126
208/230
208/240
187
254
187
252
208
208
187
228
187
228
230
240
208
254
216
252
265
277
240
293
249
291
460
480
416
508
432
504
575
600
520
635
540
630
50
230
230
198
254
208
254
400
400
344
440
360
440
Notes:
1.
Operating voltage is the min and max voltage for which the unit can function. Never
operate outside of this min and max voltage.
2.
The Acceptable Performance Range is the min and max voltage for which the unit
performance is designed and rated to give acceptable performance.
Route power and control wiring, separately,
through the utility entry in the unit. Do not
run power and control signal wires in the
same conduit.
All units require field supplied electrical
overcurrent and short circuit protection.
Device must not be sized larger than the
Maximum Overcurrent Protection (MOP)
shown on the unit nameplate.
Codes may require a disconnect switch be
within sight of the unit.
It is recommended that the field installed
overcurrent protection or disconnect switch
not be installed on the unit.
On units with external control box, electrical
supply can enter through either side of the
controls compartment.
Figure 15 - External control box electrical
connections
The
foam
insulation
releases
dangerous fumes when it is burnt. Do
not cut a foam part with a cutting torch
or plasma cutter. Do not weld to a
foam filled part.
WARNING